UPS Type
Line Interactive
Backup Time (Half/Full Load)
37 min/15.50 min
Standards
Tested to CE/ IEC 60601-1 (Series AGOM6832), Class B (emissions)
NEMA Plug Configuration
C14
NEMA Receptacle Configuration
(6) C13
Transfer Time
5 milliseconds AC to battery; 8 milliseconds battery to AC
AC Mode BTU / Hr. (Full Load)
15.6
Individually Controllable Load Banks
No
AC Suppression Response Time
Instantaneous
Audible Alarm
Audible alarm indicates power failure conditions, silenceable via alarm cancel switch. Once cancelled, alarm will resume when approximately 2 minutes of battery operation remain (assuming full load)
Cold Start (Startup in Battery Mode During a Power Failure)
Cold-start operation supported
Grounding Lug
Ground Potential Equalization Connector: POAG-S6/20
Output AC Waveform (Battery Mode)
PWM sine wave
Battery Access
Battery access door allows hot-swap battery replacement without powering connected equipment off
Frequency Compatibility Details
Automatic frequency selection
Switches
Yes, includes 2 front panel mounted push-button switches for system enable, self-test and alarm cancel functions
UPS Input Connection Description
C14 inlet accepts user-supplied AC power cord with grounded country-specific plug
Recommended Electrical Service
10A 230V
Battery Mode BTU / Hr. (Full Load)
124.5
Output Watt Capacity (Watts)
225
Dataline Suppression
2-Line Tel/DSL
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Battery Recharge Rate (Included Batteries)
Less than 7.2 hours from 10% to 90%
High Voltage Transfer to Battery Power (Setpoint)
266
Primary Form Factor
Tower
Voltage Regulation Description
Line interactive UPS offers a single boost level of brownout correction to maintain usable, computer grade output
Installation Form Factors Supported with Included Accessories
Tower
Output Voltage Regulation (Line Mode)
-18%, +8%
Voltage Compatibility (VAC)
230
Relative Humidity
0 to 95%, non-condensing
UPS Certifications
CE; Tested to UL60601-1 (medical grade)
Low Voltage Transfer to Battery Power (Setpoint)
159
LED Indicators
4 LEDs indicate line power, battery power, overload and battery low/replace status
EMI / RFI AC Noise Suppression
Yes
Undervoltage Correction
Input voltages between 159 and 199 are boosted by 14%
DC System Voltage (VDC)
12
Nominal Input Voltage(s) Supported
230V AC
Communications Interface
USB
Full Load Runtime (min.)
15.5 min. (225w)
Installation Form Factors Supported with Optional Accessories
Wallmount (UPSWM - tower mounting kit)
Half Load Runtime (min.)
37 min. (115w)
Output Volt Amp Capacity (VA)
350
Cooling Method
Convection
Nominal Output Voltage(s) Supported
220V; 230V; 240V
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Rated input current (Maximum Load)
1.8A
Internal UPS Replacement Battery Cartridge
RBC52 (quantity 2)
Additional Information
Input Receptacle: C14, Output Receptacles: 6 x C13
Package Contents
OmniSmart OMNIX350HG 350VA Tower UPS, USB Cables, Telephone Cable, Warranty Information, Instruction Manual
Load Capacity
350 VA/225 W
Typical Battery Recharge Time
7.20 Hour