CCC, CE Certified, CSA Certified, EAC, EN/IEC 60255-1, GL, RCM, UL Listed
Contact Form
DPDT
Item
Monitor Relay
Response Time
<= 500 ms
Trip Point
Adjustable 0.01 to 1.00 A
Trip Delay
0.1 to 30 sec
Electrical Connection
Terminal Strip
Type of Output
Relay
Sensing Amp Range
0.01 to 1.00 A
Input or Control Voltage
20 to 264 V AC/DC
Core Type - Relay
Solid
Power Consumption
3.5 VA
Input Voltage
24 to 240V AC/DC
Mechanical Operating Durability
10,000,000
Weight
0.24 lb
Maximum Operating Temperature
158 Degrees F
Maximum Switching Capacity
2,000 VA
Number of Pins
9
Current Rating
8 A
IP Rating
IP20; IP40; IP50
Contact Rating (DC)
0.01 A @ 5V
Contact Rating (AC)
8 A @ 250V
Minimum Operating Temperature
-40 Degrees F
Monitored Parameters
Overcurrent, Undercurrent
Mounting Style
DIN Rail
Minimum Switching Current
10 mA
Maximum Switching Voltage
250V AC
Control Circuit Voltage Limits
15 % + 10 % Un
Ambient Air Temperature For Operation
-20-50°C 60 Hz || -20-60°C 50 Hz
Dielectric Test Voltage
2.5 kV AC 50 Hz, 1 min IEC 60255-27
Relay Monitored Parameters
overcurrent or undercurrent detection || overcurrent or undercurrent in window mode
Relay Type
current control relay
Time Delay Drift
<= 0.05 % per degree centigrade depending permissible ambient air temperature || <= 1 % within the supply voltage range
Maximum Power Consumption In Va
3.5 VA
Tightening Torque
0.6-1 N.m IEC 60947-1
Maximum Power Consumption In W
1.5 W DC
Run-Up Delay At Power-Up
0.3 s
Ambient Air Temperature For Storage
-40-70°C
Mounting Support
35 mm DIN rail conforming to EN/IEC 60715
Threshold Setting
10...100 %
Relay Name
RM22JA
Reset Time
1500 ms at maximum voltage
Connections - Terminals
screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end || screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
Setting Accuracy Of The Switching Threshold
+/- 10 % of the full scale
Local Signalling
for relay ON LED (yellow) || for power ON LED (green)
Repeat Accuracy
+/- 0.5 % input and measurement circuit || +/- 0.2 % time delay
Pollution Degree
3 IEC 60664-1 || 3 UL 508
Overvoltage Category
III IEC 60664-1 || III UL 508
Electrical Durability
100000 cycles
Measurement Range
4...40 mA E1-M terminals || 20...200 mA E2-M terminals || 100...1000 mA E3-M terminals || 4 mA...1 A current AC/DC 50/60 Hz
Output Contacts
2 C/O
Contacts Material
cadmium free
Setting Accuracy Of Time Delay
0.916666666666667
Measurement Error
< 1 % over the whole range with voltage variation || 0.05 %/°C with temperature variation
immunity for residential, commercial and light-industrial environments EN/IEC 61000-6-1 || immunity for industrial environments EN/IEC 61000-6-2 || emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3 || emission standard for industrial environments EN/IEC 61000-6-4 || electrostatic discharge 6 kV contact discharge)level 3 IEC 61000-4-2 || electrostatic discharge 8 kV air discharge)level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test 10 V/mlevel 3 IEC 61000-4-3 || electrical fast transient/burst immunity test 4 kV direct)level 4 IEC 61000-4-4 || electrical fast transient/burst immunity test 2 kV capacitive coupling)level 4 IEC 61000-4-4 || surge immunity test 4 kV common mode)level 4 IEC 61000-4-5 || surge immunity test 2 kV differential mode)level 4 IEC 61000-4-5 || conducted and radiated emissionsclass B group 1 CISPR 11 || conducted and radiated emissionsclass B CISPR 22
Maximum Measuring Cycle
100 ms measurement cycle as true rms value
Shock Resistance
15 gn 11 ms) not in operation IEC 60068-2-27 || 5 gn 11 ms) in operation IEC 60068-2-27
Mechanical Durability
10000000 cycles
Switching Capacity In Va
2000 VA
Insulation Resistance
> 100 MOhm 500 V DC IEC 60255-27
Supply Voltage Limits
20.4-264 V AC/DC
Vibration Resistance
0.075 mm 10-58.1 Hz) not in operation IEC 60068-2-6 || 1 gn 10-58.1 Hz) not in operation IEC 60068-2-6 || 0.035 mm 58.1-150 Hz) in operation IEC 60068-2-6 || 0.5 gn 58.1-150 Hz) in operation IEC 60068-2-6
Immunity To Microbreaks
50 ms
Time Delay Type
adjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt
Monitor Relay, Contact Form DPDT, Contact Rating (AC) 8 A @ 250V, Contact Rating (DC) 0.01 A @ 5V, Current Rating 8 A, Input Voltage 24 to 240V AC/DC, Monitored Parameters Overcurrent, Undercurrent, Mounting Style DIN Rail, Number of Pins 9, Trip Point Adjustable 0.01 to 1.00 A, Electrical Connection Terminal Strip, Body Depth 3.13 in, Body Height 3.54 in, Body Width 0.89 in