- Item
- Compact Smart Relay
- Output Type
- (8) Transistor
- Number of Outputs
- 8
- Number of Inputs
- 12
- Features
- Built-In Epsom Flash Memory, Zelio Soft Programming Software included, Malfunctions Diagnosing Display, Simple Programming
- Counters
- 16
- Input Voltage
- 24V AC/DC
- Timers
- 16
- Display
- LCD
- Clock
- Yes
- Amps
- 8 A
- Response Time
- <= 1 ms from state 0 to state 1)transistor output || <= 1 ms from state 1 to state 0)transistor output
- Standards
- C-Tick, CSA, EN/IEC 60068-2-6 FC, EN/IEC 61000-4-11, GL, GOST, UL Listed
- Product Type
- Compact Smart Relay
- Voltage State 1 Guaranteed
- >= 15 V I1 to IA and IH to IR discrete input circuit || >= 15 V IB to IG used as discrete input circuit
- [Ures] Residual Voltage
- 2 V at state 1 transistor output
- Disturbance Radiated/Conducted
- class B EN 55022-11 group 1
- Current State 0 Guaranteed
- <= 0.5 mA IB to IG used as discrete input circuit) || <= 0.75 mA I1 to IA and IH to IR discrete input circuit)
- Clock Drift
- 12 min/year 0-55 °C || 6 s/month 25-25 °C
- Connections - Terminals
screw terminals, 1 x 0.2 to 1 x 2.5 mm² AWG 25 to AWG 14) semi-solid || screw terminals, 1 x 0.2 to 1 x 2.5 mm² AWG 25 to AWG 14) solid || screw terminals, 1 x 0.25 to 1 x 2.5 mm² AWG 24 to AWG 14) flexible with cable end || screw terminals, 2 x 0.2 to 2 x 1.5 mm² AWG 24 to AWG 16) solid || screw terminals, 2 x 0.25 to 2 x 0.75 mm² AWG 24 to AWG 18) flexible with cable end
- Tightening Torque
- 0.5 N.m
- Operating Altitude
- 6561.68 ft (2000 m)
- Output Voltage
- 24 V transistor output
- Analogue Input Type
- common mode
- Ambient Air Temperature For Storage
- -40-70 °C
- Environmental Characteristic
- EMC directive EN/IEC 61000-6-2 || EMC directive EN/IEC 61000-6-3 || EMC directive EN/IEC 61000-6-4 || EMC directive EN/IEC 61131-2 zone B || low voltage directive EN/IEC 61131-2
- Output Voltage Limits
- 19.2 to 30 V DC transistor output)
- Repeat Accuracy
- +/- 2 % 55 °C analogue input circuit
- Local Display
- with
- Immunity To Microbreaks
- 1 ms
- Current State 1 Guaranteed
- >= 1.2 mA IB to IG used as discrete input circuit) || >= 2.2 mA I1 to IA and IH to IR discrete input circuit)
- Analogue Input Number
- 6
- Operating Distance
- 10 m between stations, with screened cable (sensor not isolated) analogue input circuit
- Number Or Control Scheme Lines
- 0-240 ladder || 0-500 FBD
- Backup Time
- 10 years 25 °C
- Ip Degree Of Protection
- IP20 IEC 60529 terminal block) || IP40 IEC 60529 front panel)
- Input Impedance
- 12 kOhm IB to IG used as analogue input circuit || 12 kOhm IB to IG used as discrete input circuit || 7.4 kOhm I1 to IA and IH to IR discrete input circuit
- Discrete Input Type
- resistive
- Voltage State 0 Guaranteed
- <= 5 V I1 to IA and IH to IR discrete input circuit || <= 5 V IB to IG used as discrete input circuit
- Relative Humidity
- 95-95 % without condensation or dripping water
- Maximum Permissible Voltage
- 30 V analogue input circuit
- Overvoltage Protection
- with transistor output
- Conversion Error
- +/- 5 % 25 °C analogue input circuit || +/- 6.2 % 55 °C analogue input circuit
- Product Certifications
- CSA || UL || GOST || GL || C-tick
- Reverse Polarity Protection
- with
- Power Dissipation In W
- 3 W without extension
- Discrete Input Voltage
- 24 V DC
- Counting Frequency
- 1 kHz discrete input
- Supply Voltage Limits
- 19.2-30 V
- Overvoltage Category
- III EN/IEC 60664-1
- Cycle Time
- 6-90 ms
- Checks
- program memory on each power up
- Conversion Time
- smart relay cycle time analogue input circuit
- Temperature Probe Type
- NTC 10k 25 °C || NTC 1000k 25 °C || KTY81 210/220/221/222/250 || Pt 500
- Discrete Input Current
- 4 mA
- [Us] Rated Supply Voltage
- 24 V DC
- Short-Circuit Protection
- with transistor output
- Product Or Component Type
- compact smart relay
- Maximum Altitude Transport
- 3048 m
- Overload Protection
- with transistor output
- Discrete Input Number
- 12 EN/IEC 61131-2 type 1
- Lsb Value
- 39 mV analogue input circuit
- Ambient Air Temperature For Operation
- -20-40 °C in non-ventilated enclosure IEC 60068-2-1 and IEC 60068-2-2 || -20-55 °C IEC 60068-2-1 and IEC 60068-2-2
- Load Current
- 0.5-0.625 A transistor output
- Maximum Supply Current
- 100 mA without extension)
- Pollution Degree
- 2 EN/IEC 61131-2
- Analogue Input Range
- 0 to 10 V || 0 to 24 V
- Analogue Input Resolution
- 8 bits
- Input Compatibility
- 3-wire proximity sensors PNP discrete input
- Number of Counters
- 16
- Mounting Style
- DIN Rail
- Current
- 8 A
- Input Circuit Voltage - Maximum
- 24 V DC
- DC Voltage Rating
- 24V DC
- Output Circuit Voltage - Minimum
- 5 V DC, 24 V AC
- AC Voltage Rating
- 24V AC
- Clock Included
- Clock Included
- Series
- SR2
- Output Circuit Current - Maximum
- 8 A
- Input Type
- (12) Resistive
- Input Circuit Current - Maximum
- 4 mA
- Display Type
- LCD
- Number of Timers
- 16
- Output Circuit Voltage - Maximum
- 30 V DC, 250 V AC