Item
IEC Magnetic Contactor
Auxiliary Contact Form
No Auxiliary Contacts
Reversing Capability
Reversing
Terminal Connection Type
Screw Clamp
Number of Auxillary Contacts
1
Standards
BS 5424, CSA, IEC 60947, NF C 63-110, UKCA, UL Listed, VDE 0660
Frame / Series / Class / Code
TeSys
Enclosure NEMA Rating
No Enclosure
Vibration Resistance
4 G (Contactor Closed), 2 G (Contactor Open)
Rated Short-Time Withstand Current
90 A (at 50°C for 1 s Power Circuit), 85 A (at 50°C for 5 s Power Circuit), 80 A (at 50°C for 10 s Power Circuit), 60 A (at 50°C for 30 s Power Circuit), 45 A (at 50°C for 1 min Power Circuit), 40 A (at 50°C for 3 min Power Circuit), 80 A (For 1 s Signalling Circuit), 90 A (For 500 ms Signalling Circuit), 110 A (For 100 ms Signalling Circuit), 20 A (at 50°C for 15 min Power Circuit)
Fuse Amps
25 A (Power Circuit), 10 A (Signalling Circuit)
Control Circuit Voltage Limits
Operational: 0.8 to 1.15 Uc (at 50°C), Drop-Out: 0.2 to 0.75 Uc (at 50°C)
Max. Operating Watts
1.5 kW (at 220 to 230V AC 50/60 Hz), 2.2 kW (at 380 to 415VAC 50/60 Hz), 3 kW (at 440V AC 50/60 Hz), 3 kW (at 480V AC 50/60 Hz), 3 kW (at 500 to 600V AC 50/60 Hz), 3 kW (at 660 to 690V AC 50/60 Hz)
Impulse Withstand Voltage
8 kV
Electrical Durability
1.3 Mcycles (6 A, AC-3, Less than 440 V); 1.3 Mcycles (6 A, AC-3e, Less than 440 V)
Rated Making Capacity
110 A
Switching Voltage
17 V (Signalling Circuit)
Tightening Torque
0.8 to 1.3 Nm
Switching Current
5 mA (Signalling Circuit)
Rated Insulation Volts
600/690V
Mechanical Durability
5 Mcycles
Operating Speed
3600 cycles per hr
Rated Breaking Capacity
110 A @ 415V, 440V, 220 to 230V, 380 to 400 V; 80 A @ 500V; 70 A @ 660 to 690V
Fire Rating
UL 94 V1, NF F 16-101, NF F 16-102
Application
Motor Control
Shock Resistance
10 G for 11 ms (on X axis with Contactor Closed), 15 G for 11 ms (on Y and Z axis with Contactor Closed), 6 G for 11 ms (on X axis with Contactor Open), 10 G for 11 ms (on Y and Z axis with Contactor Open)
Operating Time
10 to 20 ms (Coil Energisation and NO Closing), 10 to 20 ms (Coil De-Energisation and NO Opening)
Overvoltage Category
CAT III
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Environmental Attributes
Mercury Free, Toxic Heavy Metal Free
Signalling Circuit Frequency
Less Than 400 Hz
Features
Preassembled with Reversing Power Busbar
Resistance Properties
Insulation Resistant
Number of Normally Open Main Contacts
3
Maximum Operating Temperature
122 Degrees F
Electrical Operating Durability
1,300,000
Mechanical Operating Durability
5,000,000
Embedded Surge Suppressor
No
Maximum Voltage Rating
690V AC
Mounting Style
DIN Rail, Plate
NEMA Enclosure Rating
No Enclosure
Minimum Operating Temperature
-13 Degrees F
Full Load Current - Inductive
6:00 AM
Includes Auxiliary Contacts
Yes
Inrush Power in VA
30 VA (at 68°F (20°C))
Rated Operational Voltage
Power circuit 690 V AC 50/60 Hz; Signalling circuit Less than or Equal to 690 V AC 50/60 Hz
Interlocking Type
Mechanical
Conventional Free Air Thermal Current
20 A (at 140°F (60°C)) for power circuit; 10 A (at 122°F (50°C)) for signalling circuit
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Rated Operational Current
6 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-3 for power circuit; 6 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-3e for power circuit
Operating Altitude
6561.68 ft (2000 m) without derating
Device Application
Control
Mechanical Robustness
Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27; Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27; Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27; Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27; Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27; Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27; Vibrations contactor closed4 Gn, 5 to 300 Hz IEC 60068-2-6; Vibrations contactor opened2 Gn, 5 to 300 Hz IEC 60068-2-6
Auxiliary Contacts Type
Instantaneous 1 NO
Maximum Operating Rate
3600 cyc/h
Control Circuit Voltage
24 V AC 50/60 Hz
Ambient Air Temperature For Operation
-13 to 122°F (-25 to 50°C)
Utilisation Category
AC-3; AC-3e; AC-4
Control Circuit Type
AC 50/60 Hz
Ambient Air Temperature For Storage
-58 to 176°F (-50 to 80°C)
Non Overlap Distance
0.02 in (0.5 mm)
Protective Treatment
TC IEC 60068; TC DIN 50016
Pole Contact Composition
3 NO