Item
IEC Miniature Magnetic Contactor
Auxiliary Contact Form
1NC
Reversing Capability
Reversing
Terminal Connection Type
Screw Clamp
Number of Auxillary Contacts
1
Standards
BS 5424, CSA, IEC 60947, NF C 63-110, UKCA, UL Listed, VDE 0660
Frame / Series / Class / Code
TeSys
Enclosure NEMA Rating
No Enclosure
HP @ 1 Phase - 230V
1-1/2
Operating Speed
3600 cycles per hr
Fire Rating
UL 94 V1, NF F 16-101, NF F 16-102
Vibration Resistance
4 G (Contactor Closed), 2 G (Contactor Open)
Control Circuit Voltage Limits
Operational: 0.8 to 1.15 Uc (at 50°C), Drop-Out: 0.2 to 0.75 Uc (at 50°C)
Application
Motor Control
Overvoltage Category
CAT III
Operating Time
10 to 20 ms (Coil Energisation and NO Closing), 10 to 20 ms (Coil De-Energisation and NO Opening)
Shock Resistance
10 G for 11 ms (on X axis with Contactor Closed), 15 G for 11 ms (on Y and Z axis with Contactor Closed), 6 G for 11 ms (on X axis with Contactor Open), 10 G for 11 ms (on Y and Z axis with Contactor Open)
Rated Short-Time Withstand Current
90 A (at 50°C for 1 s Power Circuit), 85 A (at 50°C for 5 s Power Circuit), 80 A (at 50°C for 10 s Power Circuit), 60 A (at 50°C for 30 s Power Circuit), 45 A (at 50°C for 1 min Power Circuit), 40 A (at 50°C for 3 min Power Circuit), 80 A (For 1 s Signalling Circuit), 90 A (For 500 ms Signalling Circuit), 110 A (For 100 ms Signalling Circuit), 20 A (at 50°C for 15 min Power Circuit)
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Signalling Circuit Frequency
Less Than 400 Hz
Rated Breaking Capacity
110 A @ 415V, 440V, 220 to 230V, 380 to 400 V; 80 A @ 500V; 70 A @ 660 to 690V
Switching Voltage
17 V (Signalling Circuit)
Fuse Amps
25 A (Power Circuit), 10 A (Signalling Circuit)
Electrical Durability
1.3 Mcycles (6 A, AC-3, Less than 440 V); 1.3 Mcycles (6 A, AC-3e, Less than 440 V)
Impulse Withstand Voltage
8 kV
Mechanical Durability
5 Mcycles
Features
Preassembled with Reversing Power Busbar
Switching Current
5 mA (Signalling Circuit)
Environmental Attributes
Mercury Free, Toxic Heavy Metal Free
Tightening Torque
0.8 to 1.3 Nm
Rated Insulation Volts
600/690V
Rated Making Capacity
110 A
Max. Operating Watts
1.5 kW (at 220 to 230V AC 50/60 Hz), 2.2 kW (at 380 to 415VAC 50/60 Hz), 3 kW (at 440V AC 50/60 Hz), 3 kW (at 480V AC 50/60 Hz), 3 kW (at 500 to 600V AC 50/60 Hz), 3 kW (at 660 to 690V AC 50/60 Hz)
Full Load Current - Inductive
6:00 AM
Resistance Properties
Insulation Resistant
Minimum Operating Temperature
-13 Degrees F
Mounting Style
DIN Rail, Plate
Mechanical Operating Durability
5,000,000
Horsepower @ Three Phase - 208V AC
1 1/2 hp
Maximum Voltage Rating
690V AC
Includes Auxiliary Contacts
Yes
Number of Normally Open Main Contacts
3
Horsepower @ Single Phase - 240V AC
1 1/2 hp
Horsepower @ Single Phase - 120V AC
1/2 hp
Embedded Surge Suppressor
No
Horsepower @ Three Phase - 240V AC
1 1/2 hp
Horsepower @ Three Phase - 480V AC
3 hp
Full Load Current - Resistive
15 A
Maximum Operating Temperature
122 Degrees F
NEMA Enclosure Rating
No Enclosure
Electrical Operating Durability
1,300,000
Horsepower @ Three Phase - 600V AC
3 hp
Conventional Free Air Thermal Current
20 A (at 50°C Power Circuit), 10 A (at 50°C Signalling Circuit)