- Item
- Manual Motor Starter
- Number of Poles
- 3
- Operator
- Toggle
- Phase
- 3
- Current AC
- 6.3 A
- Series
- TeSys Deca
- Standards
- EN/IEC 60947-2 || EN/IEC 60947-4-1
- Ik Degree Of Protection
- IK04
- Rated Duty
- continuous IEC 60947-4-1
- Tightening Torque
- 1.7 N.m screw clamp terminal
- Trip Unit Technology
- thermal-magnetic
- Motor Power Kw
1.1-1.1 kW 220/230 V AC 50/60 Hz motor protection high peak current || 2.2-2.2 kW 400/415 V AC 50/60 Hz motor protection high peak current || 2.2-2.2 kW 440 V AC 50/60 Hz motor protection high peak current || 3-3 kW 440 V AC 50/60 Hz motor protection high peak current || 3-3 kW 500 V AC 50/60 Hz motor protection high peak current || 4-4 kW 690 V AC 50/60 Hz motor protection high peak current || 1.6-1.6 kW 230/240 V AC 50/60 Hz transformer protection || 2-2 kW 230/240 V AC 50/60 Hz transformer protection || 2.5-2.5 kW 400/415 V AC 50/60 Hz transformer protection || 2.5-2.5 kW 440 V AC 50/60 Hz transformer protection || 4-4 kW 440 V AC 50/60 Hz transformer protection || 4-4 kW 500 V AC 50/60 Hz transformer protection || 4-4 kW 690 V AC 50/60 Hz transformer protection || 5-5 kW 690 V AC 50/60 Hz transformer protection || 6.3-6.3 kW 690 V AC 50/60 Hz transformer protection
- Fire Resistance
- 960°C IEC 60695-2-11
- Network Type
- AC
- Device Short Name
- GV2RT
- Device Application
- motor protection || transformer
- Fixing Mode
- 35 mm symmetrical DIN rail clipped || panel screwed with adaptor plate)
- Utilisation Category
- category A IEC 60947-2 || AC-3 IEC 60947-4-1
- Power Dissipation Per Pole
- 2.5 W
- Ambient Air Temperature For Storage
- -40-80°C
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947-2
- Thermal Protection Adjustment Range
- 4-6.3 A IEC 60947-4-1
- Mechanical Robustness
- shocks 30 Gn for 11 ms || vibrations 5 Gn, 5 to 150 Hz
- Range
- TeSys Deca
- Operating Altitude
- 6561.68 ft (2000 m)
- Product Name
- TeSys GV2 || TeSys Deca
- Suitability For Isolation
- yes IEC 60947-1§ 7-1-6
- Climatic Withstand
- IACS E10
- Magnetic Tripping Current
- 138-138 A
- Mechanical Operating Durability
- 100,000
- Maximum Voltage Rating
- 690V AC
- IP Rating
- IP20
- Rated Service Short-Circuit Breaking Capacity
- 100 kA Icu 220/230 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2
- Electrical Operating Durability
- 100,000
- Minimum Operating Temperature
- -4 Degrees F
- Maximum Operating Temperature
- 140 Degrees F