Type of Operator
Selector Switch
Action
Maintained/Maintained
Operator Head Material
Plastic
Bezel Material
Chrome Plated Metal
Standards
BV, CSA, DNV, GL, LROS, UL Listed
Switch Operation @ Position D
No Fourth Position
Contact Rating
0.1A @ 600V DC, 0.27A @ 250 V DC, 0.55A @ 125V DC, 1.2A @ 600 V AC, 3A @ 240V AC, 6A @ 120V AC
Switch Operation @ Position C
No Third Position
Includes
ZB4BK1233, ZB4BW0G35
IP Rating
IP66, IP67, IP69, IP69K
DC Contact Rating
0.1 A @ 600 V, 0.27 A @ 250 V, 0.55 A @ 125 V
NEMA Contact Rating Designation
A600/Q600
Lamp Module Type
Full Voltage
AC Contact Rating
1.2 A @ 600 V, 3 A @ 240 V, 6 A @ 120 V
Shape Of Screw Head
cross Philips no 1 || cross pozidriv No 1 || slotted flat Ø 4 mm || slotted flat Ø 5.5 mm
Ambient Air Temperature For Storage
-40-70°C
Device Presentation
complete product
Fixing Collar Material
zamak
Electromagnetic Emission
class B IEC 55011
Mechanical Durability
1000000 cycles
Contacts Material
silver alloy (Ag/Ni)
Current Consumption
14 mA
[Uimp] Rated Impulse Withstand Voltage
6 kV EN 60947-1
Tightening Torque
0.8-1.2 N.m EN 60947-1
Surge Withstand
1 kV IEC 61000-4-5
Electrical Shock Protection Class
class I IEC 60536
Resistance To Electromagnetic Fields
10 V/m IEC 61000-4-3
Light Source
universal LED
Electrical Durability
1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C || 1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C || 1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C
Shock Resistance
30 gn 18 ms) half sine wave acceleration IEC 60068-2-27 || 50 gn 11 ms) half sine wave acceleration IEC 60068-2-27
Shape Of Signaling Unit Head
round
Connections - Terminals
screw clamp terminals, <= 2 x 1.5 mm² with cable end EN/IEC 60947-1 || screw clamp terminals, >= 1 x 0.22 mm² without cable end EN/IEC 60947-1
Operator Profile
green standard handle
Product Or Component Type
illuminated selector switch
Resistance To Electrostatic Discharge
6 kV on contact (on metal parts) IEC 61000-4-2 || 8 kV in free air (in insulating parts) IEC 61000-4-2
Vibration Resistance
5 gn 2-500 Hz)IEC 60068-2-6
Positive Opening
with EN/IEC 60947-5-1 appendix K
Product Certifications
GL || LROS (Lloyds register of shipping) || CSA || BV || UL || DNV
[Ith] Conventional Free Air Thermal Current
10 A EN/IEC 60947-5-1
Ambient Air Temperature For Operation
-40-70°C
Short-Circuit Protection
10 A cartridge fuse gG EN/IEC 60947-5-1
[Ui] Rated Insulation Voltage
600 V 3)EN 60947-1
Contacts Type And Composition
1 NO + 1 NC
Contact Operation
slow-break
[Us] Rated Supply Voltage
110 to 120 V AC 50/60 Hz
Operator Position Information
2 positions 90°
Ip Degree Of Protection
IP66 IEC 60529 || IP67 || IP69 || IP69K
Resistance To High Pressure Washer
7000000 Pa 55°C 0.1 m
Contacts Usage
standard contacts
[Ie] Rated Operational Current
3 A 240 V, AC-15, A600 EN/IEC 60947-5-1 || 6 A 120 V, AC-15, A600 EN/IEC 60947-5-1 || 0.1 A 600 V, DC-13, Q600 EN/IEC 60947-5-1 || 0.27 A 250 V, DC-13, Q600 EN/IEC 60947-5-1 || 0.55 A 125 V, DC-13, Q600 EN/IEC 60947-5-1 || 1.2 A 600 V, AC-15, A600 EN/IEC 60947-5-1
Operating Torque
0.14 N.m NO changing electrical state
Electrical Reliability
λ < 10exp(-6) 5 V 1 mA in clean environment EN/IEC 60947-5-4 || λ < 10exp(-8) 17 V 5 mA in clean environment EN/IEC 60947-5-4
Nema Degree Of Protection
NEMA 13 || NEMA 4X
Ik Degree Of Protection
IK04 IEC 50102
Supply Voltage Limits
100-132 V AC
Resistance To Fast Transients
2 kV IEC 61000-4-4
Terminals Description Iso N°1
(13-14)NO || (21-22)NC
Terminals Description Iso N°1
(13-14)NO || (21-22)NC
Switch Function @ 1st Position
Off
Hazardous Location Specification
Not Rated
Contact Block Material
Metal
Lamp Voltage - Maximum
120 V AC
Switch Function @ 2nd Position
On
Operator Head Type
Short-Handled Knob
Operator Head Color
Green
Operator Illumination
Illuminated
NEMA Enclosure Rating
1, 12, 13, 2, 3, 4, 4X
Switch Function @ 3rd Position
No Third Position
Switch Function @ 4th Position
No Fourth Position