tripping current 130 % of Ir on two phase, the last one at 0
Ambient Air Temperature For Operation
-20-60°C without derating IEC 60947-4-1
Thermal Overload Class
class 10A IEC 60947-4-1
Connections - Terminals
control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end || power circuit screw clamp terminals 1 1.5-10 mm² flexible without cable end || power circuit screw clamp terminals 1 1-4 mm² flexible with cable end || power circuit screw clamp terminals 1 1-6 mm² solid without cable end
Dielectric Strength
1.89 kV 50 Hz IEC 60947-1
Product Or Component Type
non differential thermal overload relay
Climatic Withstand
IACS E10
Thermal Protection Adjustment Range
9-13 A
Ambient Air Temperature For Storage
-60-70°C
Network Frequency
0 to 400 Hz
Tightening Torque
control circuit 1.7 N.m screw clamp terminals || power circuit 1.7 N.m screw clamp terminals
Tripping Threshold
1.14 +/- 0.06 Ir IEC 60947-4-1
Device Short Name
LR3D
Product Compatibility
LC1D32 || LC1D25 || LC1D18 || LC1D12 || LC1D38
Associated Fuse Rating
4 A gG signalling circuit || 4 A BS signalling circuit
Permissible Current
3 A 120 V AC-15 signalling circuit || 0.22 A 125 V DC-13 signalling circuit
Range
TeSys || TeSys Deca
Flame Retardance
V1 conforming to UL 94
Product Name
TeSys LRD || TeSys Deca
Rated Insulation Voltage
Power circuit 600 V CSA; Power circuit 600 V UL; Power circuit 690 V IEC 60947-4-1
Rated Operational Voltage
690 V AC 0 to 400 Hz power circuit IEC 60947-4-1
Minimum Operating Temperature
-4 Degrees F
Conventional Free Air Thermal Current
5 A signalling circuit
Mounting Style
plate, with specific accessories || rail, with specific accessories || under contactor