Shop SQUARE D

Miniature Circuit Breaker, E FRAME Series, 60A, 3 Pole, 277/480V AC, 25kA at 120V AC

  • Mfr # EDB34060SA

  • Zoro # G2278972


product price: 
$
1,425.99
/ea
Free Shipping & Returns

Key Features

Series
E FRAME
Number of Poles
3
AC Voltage Rating
277/480V AC
Circuit Breaker Type
Shunt Trip
Phase
3
See all product information
Unlock 30-day payment terms
Unlock 30-day payment terms
Business customers can apply for Net 30—no fees, no interest, fast approval. Terms apply.
Create Account
Get 10% off your order
Get 10% off your order
Sign up for our email list and receive your promo code via email.

Specifications

Details

MFR #
EDB34060SA
Zoro #
G2278972
UPC #
785901129769
Country of Origin
Korea, Republic of
Item
Miniature Circuit Breaker
Series
E FRAME
Amps
60A
Number of Poles
3
AC Voltage Rating
277/480V AC
Circuit Breaker Type
Shunt Trip
Phase
3
Circuit Breaker Actuator
Toggle
Circuit Breaker Mounting Style
Bolt On
Max. AIR Rating
25kA at 120V AC
Trip Type
Shunt Trip, Thermal Magnetic
Terminal Connection
Lugs
Phase Connection
ABC
DC Voltage Rating
Not Rated
Standards
cULus
For Use With
Square D NF Panelboards
High Amp Trip Setting
1800 A
Interrupt Rating
18 kA at 277/480Y/277V AC, 25 kA at 120/240V AC
Application
HACR rated Applications
Features
Mercury Free
Max. Operating Temp.
104 Degrees F
Compatible Panelboard/Load Center Series
NF
Voltage
480Y/277 VAC
Holding Current
630 A
Breaking Capacity
18 kA 277 V AC; 25 kA 240 V AC; 18 kA 480Y/277 V AC; 25 kA 120 V AC; 25 kA 120/240 V AC
Module Type
E-Frame
Ambient Air Temperature For Operation
104°F (40°C)
Number Of Spaces
4
Local Signalling
Trip indicator
Product Destination
NF panelboard
Tightening Torque
34.52 lbf.in (3.9 N.m) 0.00 to 0.01 in² (2.5 to 6 mm²) (AWG 14 to AWG 10); 49.56 lbf.in (5.6 N.m) 0.02 to 0.11 in² (10 to 70 mm²) (AWG 8 to AWG 2/0)
Protection Type
Overload; Short-circuit
Breaking Capacity Code
D
AWG Gauge
AWG 12 to AWG 2/0 aluminium; AWG 14 to AWG 2/0 copper
Circuit Breaker Application
HACR rated

Description

Miniature Circuit Breaker, Amps 60 A, AC Voltage Rating 277/480V AC, Circuit Breaker Type Shunt Trip, Number of Poles 3, DC Voltage Rating Not Rated, Circuit Breaker Actuator Toggle, Circuit Breaker Mounting Style Bolt On, Compatible Panelboard/Load Center Series NF, Phase Three, Series EDB, Max. AIR Rating 18kA at 277/480V AC, For Use With Square D NF Panelboards, Terminal Connection Lug, Frame Size 125A/EDB, Length 5.7 in, Width 3.9 in, Depth 4.1 in, Max. Operating Temp. 104 Degrees F

Ratings & reviews

3 reasons you can count on us

  • Supplies for every job.

    13 million items and the exact one you need.

  • When you need it fast, count on Zoro!

    4.5 million products ship in 1 day.

  • Stretch your budget further.

    Everyday low prices on the brands you love.