Item
|
Smart UPS
|
UPS Type
|
Line Interactive
|
Power Rating
|
1.5 kVA
|
Mounting
|
Rack/Tower
|
Wattage
|
1 kW
|
Input Voltage
|
120V AC
|
Output Voltage
|
120V AC
|
Backup Time (Half/Full Load)
|
19 min/7 min
|
Outlet Type
|
UPS/Surge
|
Medical Grade
|
No
|
Number of Outlets
|
8
|
Hz
|
60 Hz
|
NEMA Plug Configuration
|
5-15p
|
NEMA Receptacle Configuration
|
5-15R
|
Green Environmental Attribute
|
Product Contributes To Reducing Energy Consumption
|
Fax/Modem Line Protection
|
No
|
Ports
|
DB9 Serial, SNMP/Web Slot, USB EPO
|
Standards
|
Meets FCC Part 15 Category B (EMI), Tested to CSA (Canada), Tested to NOM (Mexico), UL1778 (USA)
|
Phase
|
1
|
Input Current
|
12 A
|
Footnotes
|
3,4,10,12
|
Display Type
|
LCD
|
Transfer Time
|
2 to 4 msec
|
Includes
|
4-Post Rack Mount Installation Kit, PowerAlert Software with USB, Serial and EPO Cables
|
Special Features
|
Advanced AVR Corrects Brownouts and Overvoltages, Pure Sine Wave Output
|
Automatic Volts Regulation
|
Yes
|
Input Connection
|
10 ft Cord with NEMA 5-15P Plug
|
Cooling Method
|
Fan
|
UPS AC Suppression Response Time
|
Instantaneous
|
Input Circuit Breakers
|
15A
|
Output Watt Capacity (Watts)
|
1350
|
Battery Mode BTU / Hr. (Full Load)
|
1012
|
Audible Noise
|
45 dBA maximum, front side 1m
|
Network Monitoring Port Description
|
Supports detailed monitoring of UPS and site power conditions
|
Included Mounting Accessory Description
|
Included 4POSTRAILKIT mounting bracket enables installation in 4 post racks from 20.5 to 36 inches (521 to 914mm)
|
Communications Interface
|
USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
|
Battery Replacement Description
|
Hot-swappable, user replaceable batteries
|
Voltage Regulation Description
|
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 147
|
Low Voltage Transfer to Battery Power (Setpoint)
|
83
|
Network UPS Tools Compatibility
|
NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at http://www.networkupstools.org/stable-hcl.html?manufacturer=Tripp Lite
|
Storage Temperature Range
|
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
|
Nominal Voltage Details
|
120v nominal output in battery mode
|
UPS Certifications
|
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category B (EMI)
|
High Availability UPS Features
|
Hot swappable batteries
|
Cold Start (Startup in Battery Mode During a Power Failure)
|
Cold-start operation supported
|
Alarm Cancel Operation
|
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
|
UPS AC Suppression Joule Rating
|
570
|
Output kW Capacity (kW)
|
1.35
|
Communications Cable
|
USB and DB9 cabling included
|
Frequency Compatibility
|
60 Hz
|
Output Receptacles
|
(8) 5-15R
|
Overvoltage Correction
|
Input voltages between 128 and 147 are reduced by 12%
|
Load Management Receptacles
|
Two switchable two-outlet 5-15R load banks
|
Output AC Waveform (Battery Mode)
|
Pure Sine wave
|
Grounding Lug
|
Back panel grounding lug
|
Network Management Cards
|
SNMPWEBCARD ; TLNETCARD ; WEBCARDLX ; RELAYIOCARD
|
UPS Input Connection Type
|
5-15P
|
Nominal Output Voltage(s) Supported
|
110V; 115V; 120V
|
Operating Temperature Range
|
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
|
DC System Voltage (VDC)
|
36
|
Installation Form Factors Supported with Included Accessories
|
4 post 19 inch rackmount
|
Output Voltage Regulation (Line Mode)
|
-21%, +8%
|
High Voltage Transfer to Battery Power (Setpoint)
|
147
|
Expandable Runtime
|
No
|
AC Mode BTU / Hr. (Full Load)
|
267
|
Recommended Electrical Service
|
15A 120V
|
Individually Controllable Load Banks
|
Yes
|
Input Phase
|
Single-Phase
|
Output Voltage Regulation (Battery Mode)
|
+/- 5%
|
Primary Form Factor
|
Rackmount
|
Output AC Waveform (AC Mode)
|
Sine wave
|
Undervoltage Correction
|
Input voltages between 83 and 107 are boosted by 14%
|
AC Mode Efficiency Rating (100% Load)
|
0.95
|
UPS Housing Material
|
Steel
|
Internal UPS Replacement Battery Cartridge
|
RBC93-2U
|
Relative Humidity
|
0 to 95%, non-condensing
|
Installation Form Factors Supported with Optional Accessories
|
2 post rackmount ( 2POSTRMKITWM ); 2-4 post front rail rackmount ( UPSHDEARKIT ); 4 post rackmount short-depth ( 4POSTRAILKITWM ); Tower ( 2-9USTAND ); Wallmount ( 2POSTRMKITWM )
|
Battery Recharge Rate (Included Batteries)
|
Less than 4.5 hours from 10% to 90% (typical, full load discharge)
|
Nominal Input Voltage(s) Supported
|
120V AC
|
Rated input current (Maximum Load)
|
12A
|
Output kVA Capacity (kVA)
|
1.5
|
Battery Access
|
Front panel battery access door
|
Switches
|
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
|
Power Factor
|
0.9
|
WatchDog Compatibility
|
Supports Watchdog application, OS and hard-reboot restart options for remote applications
|
EMI / RFI AC Noise Suppression
|
Yes
|
Front Panel LCD Display
|
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
|
Audible Alarm
|
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
|
Output Volt Amp Capacity (VA)
|
1500
|
PowerAlert Software
|
For local monitoring via the UPSâ„¢s built-in communication ports , download PowerAlert Local software at http://www.tripplite.com/poweralert
|
Typical Battery Recharge Time
|
4 Hour
|
Certifications & Standards
|
UL1778 (USA), cUL (Canada), FCC Class A (emissions), NOM (Mexico), Conforms to IEEE 587 / ANSI C62.41 specifications
|
Sound Emission (A-Weighted)
|
45 dB(A)
|
Product Name
|
SmartPro 1500RM2U UPS
|
USB
|
Yes
|
Overload Protection
|
Yes
|
Plug/Connector Type
|
NEMA 5-15P
|
Surge Energy Rating
|
570 J
|
Emergency Power OFF
|
Yes
|
Maximum Operating Temperature
|
104°F (40°C)
|
Battery Life
|
6 Year
|
Form Factor
|
Rack-mountable
|
Storage Relative Humidity
|
0% - 95%
|
Status Indicators
|
LED Indicator
|
Battery Characteristics
|
Valve-regulated
|
Storage Temperature
|
5°F (-15°C) - 122°F (50°C)
|
Replaceable Battery
|
Yes
|
DC System Voltage
|
36 V DC
|
Battery Chemistry
|
Lead Acid
|
Total Number of Expansion Slots
|
1
|
Waveform Type
|
Sine Wave
|
Network Management
|
SNMP/Webcard
|
Alarm
|
Low Battery, On Battery, Overload
|
Thermal Dissipation
|
78.25 W
|
Receptacle Detail
|
8 x NEMA 5-15R
|
Package Contents
|
SmartPro 1500RM2U UPS, Mounting hardware for 4 post rackmount installation, Cabling for USB & DB9 monitoring and EPO switching, PowerAlert unattended shutdown and UPS/Power monitoring software, Warranty information
|
Hot Swappable
|
Yes
|
Product Line
|
SmartPro
|
Maximum Operating Elevation
|
6561.68 ft
|
Load Capacity
|
1500 VA/1350 W
|