- VA Rating - UPS Systems
- 1.5 kVA
- Item
- UPS System
- UPS Type
- Line Interactive
- Power Rating
- 1.5kVA
- Mounting
- Tower/Wall
- Wattage
- 940 W
- Input Voltage
- 120V AC
- Output Voltage
- 110/115/120V AC
- Backup Time (Half/Full Load)
- 11.5 min/4.5 min
- Outlet Type
- (3) Surge; (5) UPS/Surge
- Medical Grade
- No
- Number of Outlets
- 8
- Phase
- Single
- Transfer Time
- 2 to 4 msec
- NEMA Receptacle Configuration
- (8) 5-15R
- Special Features
- Hot Swappable Batteries
- Automatic Volts Regulation
- Yes
- Hz
- 60 Hz
- NEMA Plug Configuration
- 5-15P
- Green Environmental Attribute
- Product Contributes To Reducing Energy Consumption
- Fax/Modem Line Protection
- Yes
- Includes
- Interactive UPS, USB and Telephone Cable
- Display Type
- No Display
- Standards
- CSA, FCC Part 15 Class B, NOM, RoHS, UL1778
- Ports
- TEL/DSL, USB
- Footnotes
- USB and TEL/DSL
- Input Current
- 12 A
- Capacity - Batteries
- 1500 VA/940 W
- Input Connection
- NEMA 5-15P Plug
- Battery Type
- VRLA
- Housing Material
- Polycarbonate
- High Availability UPS Features
- Hot swappable batteries
- AC Mode BTU / Hr. (Full Load)
- 109
- Storage Temperature Range
- +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
- Rated input current (Maximum Load)
- 12A
- Communications Cable
- USB interface cable included
- EMI / RFI AC Noise Suppression
- Yes
- UPS AC Suppression Response Time
- Instantaneous
- Input Frequency
- 60Hz +/-5%
- Battery Replacement Description
- Hot-swappable, user replaceable batteries
- Nominal Output Voltage(s) Supported
- 110V; 115V; 120V
- Communications Interface
- USB (HID enabled)
- Audible Alarm
- Audible alarm indicates power-failure and low-battery conditions
- Output Watt Capacity (Watts)
- 940
- Output Volt Amp Capacity (VA)
- 1500
- WatchDog Compatibility
- Supports Watchdog application, OS and hard-reboot restart options for remote applications
- Full Load Runtime (min.)
- 4.5 min. (940w)
- UPS Certifications
- Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category B (EMI)
- Low Voltage Transfer to Battery Power (Setpoint)
- 75
- Input Phase
- Single-Phase
- Hot-Swap PDU options
- PDUB15 (2U / 8 5-15R outlets)
- Half Load Runtime (min.)
- 11.5 min. (470w)
- Overvoltage Correction
- Input voltages between 128 and 147 are reduced by 12%
- AC Mode Efficiency Rating (100% Load)
- 0.97
- Output Voltage Regulation (Line Mode)
- -18%, +8%
- Alarm Cancel Operation
- Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status
- Severe Undervoltage Correction
- Input voltages between 75 and 92 are boosted by 30%
- Installation Form Factors Supported with Optional Accessories
- Wallmount (UPSWM - tower mounting kit)
- Recommended Electrical Service
- 15A 120V
- Undervoltage Correction
- Input voltages between 93 and 107 are boosted by 14%
- Cold Start (Startup in Battery Mode During a Power Failure)
- Cold-start operation supported
- PowerAlert Software
- For local monitoring via the UPSâ„¢s built-in USB port, download PowerAlert Local software at http://www.tripplite.com/poweralert
- LED Indicators
- 5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
- Battery Mode BTU / Hr. (Full Load)
- 523
- Internal UPS Replacement Battery Cartridge
- RBC24-SLT
- Installation Form Factors Supported with Included Accessories
- Tower
- Expandable Runtime
- No
- Battery Access
- Battery access door
- Operating Temperature Range
- +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
- DC System Voltage (VDC)
- 24
- Output kVA Capacity (kVA)
- 1.5
- UPS AC Suppression Joule Rating
- 510
- Battery Recharge Rate (Included Batteries)
- Less than 4 hours from 10% to 90%
- UPS Dataline Suppression
- 1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
- Primary Form Factor
- Tower
- Output AC Waveform (Battery Mode)
- PWM sine wave
- Voltage Regulation Description
- Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 75 to 147
- Nominal Input Voltage(s) Supported
- 120V AC
- Individually Controllable Load Banks
- No
- Relative Humidity
- 0 to 95%, non-condensing
- Switches
- 2 Switches control off/on power status and alarm-cancel/self-test operation
- Network UPS Tools Compatibility
- NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at NUT UPS Compatibility Lis
- High Voltage Transfer to Battery Power (Setpoint)
- 147
- Output Voltage Regulation (Battery Mode)
- +/- 5%
- Dataline Protection
- RJ-45, RJ-11
- Typical Battery Recharge Time
- 4 Hour
- Hot Swappable
- Yes
- USB
- Yes
- Product Series
- VS
- Additional Information
Switches: Includes 2 front panel switches one main on/off power switch and one dual function "alarm cancel" / "self test" button, Typical Application: Entry-level PCs, networked workstations, point-of-sale equipment, small business phone systems, audio/video equipment and home theater systems; Ideal for sensitive electronic applications in areas where brownout conditions are common
- Form Factor
- Tower
- Package Contents
- Omni VS 1500VA Tower UPS, USB and telephone cable, User manual with warranty information
- Load Capacity
- 1500 VA/940 W
- Output Capacity (VA)
- 1500
- Output Capacity (Watts)
- 940
- Product Compliance
- FCC Part 15 Class B (USA)
- Package Includes
- OMNIVS1500 Line-Interactive UPS;USB and telephone cable;Owner's manual with warranty information
- Product Certifications
- CSA (Canada); NOM (Mexico); UL 1778
- UPS Applications
- Home/Office Desktop; High-End Desktop/Small Network; Retail/Point of Sale; Hospitality
- Battery Recharge Time
- 4 hr
- Manufacturer Warranty
- 3 yr Limited
- Number of Outlets - UPS
- 5
- Operating Temperature - Maximum
- 104 Degrees F
- External Battery Compatible
- Not External Battery Pack Compatible
- Visible Indicator Light Conditions
- Battery Low, Overload, Power Status, Replace Battery, Voltage Regulation
- Receptacle Configuration
- 5-15R
- Power Rating - Apparent
- 1.5 kVA
- Battery Chemistry
- Valve Regulated Lead Acid
- Transfer Time - Minimum
- 2 msec
- Plug Configuration
- 5-15P
- Output Ports Included
- USB
- Power Rating - Real
- 940 W
- Run Time - Full Load
- 4.5 min
- Data Line Protection
- Includes Data Line Surge Protection
- Automatic Voltage Regulation
- Includes Automatic Voltage Regulation
- Includes Battery
- Battery Included
- Number of Outlets - Surge Only
- 3
- Operating Temperature - Minimum
- 32 Degrees F
- Input Current - Maximum
- 12 A
- Audible Alarm Conditions
- Low Battery
- Frequency
- 60 Hz
- Replacement Battery Part Number
- RBC24-SLT
- Transfer Time - Maximum
- 4 msec