Key Features

Auxiliary Contact Form
1NC/1NO
Coil Voltage
110V AC
Number of Poles
4
Full Load Amps-Inductive
25 A
Full Load Amps-Resistive
40 A
See all product information
Unlock 30-day payment terms
Unlock 30-day payment terms
Business customers can apply for Net 30—no fees, no interest, fast approval. Terms apply.
Create Account
Get 10% off your order
Get 10% off your order
Sign up for our email list and receive your promo code via email.

Specifications

Details

MFR #
LC1D258F7
Zoro #
G0569250
UPC #
785901666806
Country of Origin
Indonesia
Item
IEC Magnetic Contactor
Auxiliary Contact Form
1NC/1NO
Coil Voltage
110V AC
Number of Poles
4
Full Load Amps-Inductive
25 A
Full Load Amps-Resistive
40 A
Reversing Capability
Non-Reversing
Terminal Connection Type
Screw Clamp
Number of Auxillary Contacts
2
Standards
CB, CCC, CSA, CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, EAC, EN 60947-4-1, EN 60947-5-1, EU-RO-MR by DNV-GL, GB/T 14048.4, IEC 60947-4-1, IEC 60947-5-1, UKCA, UL 60947-5-1, UL Listed, UL 60947-4-1
Reversing
No
Frame / Series / Class / Code
TeSys
Series
TeSys Deca
Enclosure NEMA Rating
No Enclosure
Rated Making Capacity
140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit), 450 A @ 440V (Power Circuit)
Rated Breaking Capacity
450 A @ 440V
Fuse Amps
10 A (Signalling Circuit), 63 A (Type 1 Power Circuit), 40 A (Type 2 Power Circuit)
Vibration Resistance
4 G (Contactor Closed), 2 G (Contactor Open)
Watts Loss
2 to 3W
Inrush VA
70 VA
Overvoltage Category
CAT III
Rated Insulation Volts
600/690V
Mechanical Durability
15 Mcycles
Electrical Durability
1.4 Mcycles (40 A, AC-1, Less than 440 V)
Tightening Torque
1.7 Nm (Control Circuit), 1.8 Nm (Power Circuit)
Net Weight
0.425 kg
IP Rating
IP20
Shock Resistance
8 G for 11 ms (Contactor Open), 15 G for 11 ms (Contactor Closed)
Fire Rating
UL 94 V1
Non-Overlap Time
1.5 ms
Features
Without Built-In Suppressor Module
Hold VA
7.5 VA (at 60 Hz 20°C), 7 VA (at 50 Hz 20°C)
Application
Resistive Load
Switching Current
5 mA (Signalling Circuit)
Switching Voltage
17 V (Signalling Circuit)
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Impedance
2 mOhm
Operating Speed
3600 cycles per hr
Control Circuit Voltage Limits
Drop-Out AC: 0.3 to 0.6 Uc (at -40 to 60°C 50/60 Hz); Operational AC: 0.8 to 1.1 Uc (at -40 to 60°C 50 Hz), 0.85 to 1.1 Uc (at -40 to 60°C 60 Hz)
Signalling Circuit Frequency
25 to 400 Hz
Includes Protective Cover
Yes
Impulse Withstand Voltage
6 kV
Rated Short-Time Withstand Current
240 A (at 40°C for 10 s Power Circuit), 380 A (at 40°C for 1 s Power Circuit), 50 A (at 40°C for 10 min Power Circuit), 120 A (at 40°C for 1 min Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit)
Operating Time
12 to 22 ms (Closing), 4 to 19 ms (Opening)
Environmental Attributes
Mercury Free, PVC Free, Toxic Heavy Metal Free, Pollution Degree 3
Electrical Operating Durability
1,400,000
Full Load Current - Inductive
25 A
Includes Auxiliary Contacts
Yes
Maximum Operating Temperature
140 Degrees F
Number of Normally Closed Main Contacts
2
Mounting Style
DIN Rail, Plate
Embedded Surge Suppressor
No
Mechanical Operating Durability
15,000,000
Minimum Operating Temperature
-40 Degrees F
Full Load Current - Resistive
40 A
Resistance Properties
Fire Resistant, Insulation Resistant
Maximum Voltage Rating
690V AC
NEMA Enclosure Rating
No Enclosure
Frequency
50/60 Hz
Contactor Style
IEC
Number of Normally Open Main Contacts
2
Conventional Free Air Thermal Current
10 A (at 60°C Signalling Circuit), 40 A (at 60°C Power Circuit)

Description

The item is an IEC Magnetic Contactor (TeSys Deca) with 4 poles and non-reversing operation. It uses a 110 V AC coil and screw clamp terminals, and includes two auxiliary contacts configured as 1NO/1NC (2 total). It is rated for switching power circuits within specified load types and conforms to IEC standards.

Key features

  • Poles: 4
  • Coil voltage: 110 V AC
  • Auxiliary contacts: 2 total (1NO/1NC)
  • Reversing: Non-Reversing
  • Terminal type: Screw Clamp
  • Mounting: DIN Rail, Plate (Mounts on Plate, Rail)
  • Enclosure: No Enclosure; IP20
  • Series/Frame: TeSys Deca
  • Maximum voltage rating: 690 V AC
  • Rated currents: 40 A resistive; 25 A inductive
  • Rated making capacity: 140 A (AC Signalling), 250 A (DC Signalling), 450 A @ 440 V (Power Circuit)
  • Rated breaking capacity: 450 A @ 440 V
  • Frequency: 50/60 Hz
  • Impulse withstand voltage: 6 kV
  • Protective cover: Yes
  • Embedded surge suppressor: No
  • Insulation resistance: Greater than 10 MΩ (Signalling Circuit)
  • Standards: UL/CSA/IEC (example codes listed in the standards attribute)
  • Weight: 0.425 kg
  • Dimensions: Height 4.13 in; Width 1.77 in; Depth 3.9 in
  • Operating temperature range: -40°F to 140°F
  • Ratings & reviews