Item
IEC Magnetic Contactor
Auxiliary Contact Form
1NC/1NO
Reversing Capability
Non-Reversing
Terminal Connection Type
Spring Type
Number of Auxillary Contacts
2
Standards
BV, CCC, CSA, CSA C22.2 No 14, DNV, EN 60947-4-1, EN 60947-5-1, GL, GOST, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, LROS, RINA, UKCA, UL 508, UL Listed
Frame / Series / Class / Code
TeSys
Enclosure NEMA Rating
No Enclosure
HP @ 3 Phase - 575V
10 hp
Signalling Circuit Frequency
25 to 400 Hz
Fuse Amps
10 A (Signalling Circuit), 40 A (Type 1 Power Circuit), 25 A (Type 2 Power Circuit)
Rated Insulation Volts
600/690V
Impulse Withstand Voltage
6 kV
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Mechanical Durability
30 Mcycles
Operating Time
53.55 to 72.45 ms (Closing), 16 to 24 ms (Opening)
Overvoltage Category
CAT III
Shock Resistance
15 G for 11 ms (Contactor Closed), 10 G for 11 ms (Contactor Open)
Rated Making Capacity
250 A @ 440V (Power Circuit), 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit)
Max. Operating Watts
3 kW (at 220 to 230V AC 50/60 Hz AC-3), 5.5 kW (at 380 to 400V AC 50/60 Hz AC-3), 5.5 kW 415 to (at 440V AC 50/60 Hz AC-3), 7.5 kW (at 500V AC 50/60 Hz AC-3), 7.5 kW (at 660 to 690V AC 50/60 Hz AC-3), 3.7 kW (at 400V AC 50/60 Hz AC-4), 3 kW (at 220 to 230V AC 50/60 Hz AC-3e), 5.5 kW (at 380 to 400V AC 50/60 Hz AC-3e), 5.5 kW 415 to (at 440V AC 50/60 Hz AC-3e), 7.5 kW (at 500V AC 50/60 Hz AC-3e), 7.5 kW (at 660 to 690V AC 50/60 Hz AC-3e)
Application
Motor Control, Resistive Load
Electrical Durability
2 Mcycles (12 A, AC-3, Less than 440 V); 0.8 Mcycles (25 A, AC-1, Less than 440 V); 2 Mcycles (12 A, AC-3e, Less than 440 V)
Switching Voltage
17 V (Signalling Circuit)
Control Circuit Voltage Limits
Drop-Out DC: 0.1 to 0.25 Uc (at -40 to 70°C), Operational DC: 0.7 to 1.25 Uc (at -40 to 60°C), 1 to 1.25 Uc (at 60 to 70°C)
Operating Speed
3600 cycles per hr
Includes Protective Cover
Yes
Rated Breaking Capacity
250 A @ 440V
Rated Short-Time Withstand Current
105 A (at 40°C for 10 s Power Circuit), 210 A (at 40°C for 1 s Power Circuit), 30 A (at 40°C for 10 min Power Circuit), 61 A (at 40°C for 1 min Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit)
Vibration Resistance
4 G (Contactor Closed), 2 G (Contactor Open)
Switching Current
5 mA (Signalling Circuit)
Environmental Attributes
Mercury Free, PVC Free, Pollution Degree 3
Features
With Integral Suppression Device
Full Load Current - Resistive
16 A
NEMA Enclosure Rating
No Enclosure
Embedded Surge Suppressor
Yes
Horsepower @ Single Phase - 240V AC
2 hp
Full Load Current - Inductive
12:00 AM
Resistance Properties
Fire Resistant, Insulation Resistant
Horsepower @ Three Phase - 600V AC
10 hp
Horsepower @ Three Phase - 240V AC
3 hp
Horsepower @ Three Phase - 208V AC
3 hp
Electrical Operating Durability
2,000,000, 800,000
Maximum Operating Temperature
140 Degrees F
Horsepower @ Three Phase - 480V AC
7 1/2 hp
Mounting Style
DIN Rail, Plate
Number of Normally Open Main Contacts
3
Maximum Voltage Rating
690V AC
Includes Auxiliary Contacts
Yes
Horsepower @ Single Phase - 120V AC
1/2 hp
Mechanical Operating Durability
30,000,000
Minimum Operating Temperature
-40 Degrees F
Conventional Free Air Thermal Current
10 A (at 60°C Signalling Circuit), 16 A (at 60°C Power Circuit)