Item
IEC Magnetic Contactor
Auxiliary Contact Form
1NC/1NO
Reversing Capability
Reversing
Terminal Connection Type
Screw Clamp
Standards
CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508, IEC 60335-1, DNV, CSA, CCC, UL, GL, LROS, BV, RINA, GOST, UKCA, TH IEC 60068-2-30
HP @ 3 Phase - 575V
7 1/2 hp
Series
LC2D, TeSys, TeSys Deca
Rated Making Capacity
250 A @ 440V (Power Circuit), 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit)
Switching Current
5 mA (Signalling Circuit)
Mechanical Durability
30 Mcycles
Vibration Resistance
4 G (Contactor Closed), 2 G (Contactor Open)
Application
Motor Control, Resistive Load
Rated Breaking Capacity
250 A @ 440V
Impulse Withstand Voltage
6 kV
Shock Resistance
15 G for 11 ms (Contactor Closed), 10 G for 11 ms (Contactor Open)
Operating Speed
3600 cycles per hr
Includes Protective Cover
Yes
Rated Short-Time Withstand Current
30 A (at 40°C for 10 min Power Circuit), 61 A (at 40°C for 1 min Power Circuit), 105 A (at 40°C for 10 s Power Circuit), 210 A (at 40°C for 1 s Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit)
Electrical Durability
0.6 Mcycles (25 A, AC-1, Less than 440 V); 2 Mcycles (9 A, AC-3, Less than 440 V)
Features
Built-In Bi-Directional Peak Limiting Diode Suppressor; Preassembled with Reversing Power Busbar
Rated Insulation Volts
600/690V
Fuse Amps
25 A (Type 1 Power Circuit), 20 A (Type 2 Power Circuit), 10 A (Signalling Circuit)
Signalling Circuit Frequency
25 to 400 Hz
Switching Voltage
17 V (Signalling Circuit)
Max. Operating Watts
2.2 kW (at 220 to 230V AC 50 Hz), 4 kW (at 380 to 400V AC 50 Hz), 4 kW (at 415 to 440V AC 50 Hz), 5.5 kW (at 500V AC 50 Hz), 5.5 kW (at 660 to 690V AC 50 Hz)
Control Circuit Voltage Limits
Drop-Out DC: 0.1 to 0.3 Uc (at -40 to 70°C), Operational DC: 0.8 to 1.25 Uc (at -40 to 60°C), 1 to 1.25 Uc (at 60 to 70°C)
Operating Time
65.45 to 88.55 ms (Closing), 20 to 30 ms (Opening)
Tightening Torque
1.7 Nm (Control Circuit), 1.7 to 2.5 Nm (Power Circuit)
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Overvoltage Category
CAT III
Environmental Attributes
Mercury Free, PVC Free, Toxic Heavy Metal Free, Pollution Degree 3
Interlocking Type
Mechanical
Ambient Air Temperature For Storage
-76 to 176°F (-60 to 80°C)
Hold-In Power Consumption in W
2.4 W 68°F (20°C)
Maximum Operating Rate
3600 cyc/h 140°F (60°C)
Rated Operational Current
9 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-3 for power circuit; 25 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-1 for power circuit
Conventional Free Air Thermal Current
10 A (at 140°F (60°C)) for signalling circuit; 25 A (at 140°F (60°C)) for power circuit
Climatic Withstand
IACS E10; IEC 60947-1 Annex Q category D
Device Presentation
Preassembled with reversing power busbar
Rated Operational Voltage
Power circuit Less than or Equal to 690 V AC 25 to 400 Hz; Power circuit Less than or Equal to 300 V DC
Protective Treatment
TH IEC 60068-2-30
Fire Resistance
1562°F (850°C) IEC 60695-2-1
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Product Name
TeSys D; TeSys Deca
Power Dissipation Per Pole
0.2 W AC-3; 1.56 W AC-1; 0.2 W AC-3e
Inrush Power in W
2.4 W 68°F (20°C)
Control Circuit Type
DC low consumption
Mechanical Robustness
Vibrations contactor open2 Gn, 5 to 300 Hz; Vibrations contactor closed4 Gn, 5 to 300 Hz; Shocks contactor open10 Gn for 11 ms; Shocks contactor closed15 Gn for 11 ms
Utilisation Category
AC-3; AC-1; AC-3e
Auxiliary Contacts Type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1; Mirror contact 1 NC IEC 60947-4-1
Contactor Application
Resistive load; Motor control
Ambient Air Temperature For Operation
-40 to 140°F (-40 to 60°C); 140 to 158°F (60 to 70°C) with derating
Operating Altitude
0 to 9842.52 ft (0 to 3000 m)
[Ui] Rated Insulation Voltage
power circuit 690 V IEC 60947-4-1, power circuit 600 V CSA, power circuit 600 V UL, signalling circuit 690 V IEC 60947-1, signalling circuit 600 V CSA, signalling circuit 600 V UL
[Icw] Rated Short-Time Withstand Current
30 A 40°C - 10 min for power circuit, 61 A 40°C - 1 min for power circuit, 105 A 40°C - 10 s for power circuit, 210 A 40°C - 1 s for power circuit, 100 A - 1 s for signalling circuit, 120 A - 500 ms for signalling circuit, 140 A - 100 ms for signalling circuit
Full Load Current - Inductive
9:00 AM
Horsepower @ Three Phase - 240V AC
2 hp
Horsepower @ Three Phase - 480V AC
5 hp
Horsepower @ Single Phase - 240V AC
1 hp
Full Load Current - Resistive
25 A
Horsepower @ Three Phase - 208V AC
2 hp
Pole Contact Composition
3 NO
Maximum Voltage Rating
690V AC, 300V DC
Mounting Style
Plate, Rail
Maximum Operating Temperature
140 Degrees F