Item
IEC Magnetic Contactor
Auxiliary Contact Form
1NC/1NO
Coil Voltage
100V-250V AC/DC
Full Load Amps-Inductive
65 A
Full Load Amps-Resistive
80 A
Reversing Capability
Reversing
Terminal Connection Type
Screw Clamp
Number of Auxillary Contacts
2
Standards
CCC, CSA, CSA C22.2 No 60947-4-1, DNV-GL, EAC, EN/IEC 60947-4-1, EN/IEC 60947-5-1, IEC 60335-1, KC, LROS, UKCA, UL Listed, UL 60947-4-1
Coil Volts
100 to 250 V AC/DC
HP @ 3 Phase - 480V
40 hp
Enclosure NEMA Rating
No Enclosure
Aux. Contact Configuration
1NO/1NC
Frame / Series / Class / Code
TeSys
HP @ 3 Phase - 208V
20 hp
HP @ 3 Phase - 575V
50 hp
HP @ 1 Phase - 240V
10 hp
HP @ 3 Phase - 240V
20 hp
Horsepower @ Single Phase - 240V AC
10 hp
Maximum Operating Temperature
140 Degrees F
Mechanical Operating Durability
6,000,000
Horsepower @ Three Phase - 240V AC
20 hp
Horsepower @ Three Phase - 600V AC
50 hp
NEMA Enclosure Rating
No Enclosure
Horsepower @ Three Phase - 480V AC
40 hp
Horsepower @ Three Phase - 208V AC
20 hp
Resistance Properties
Fire Resistant, Insulation Resistant
Horsepower @ Single Phase - 120V AC
5 hp
Includes Auxiliary Contacts
Yes
Embedded Surge Suppressor
No
Mounting Style
DIN Rail, Plate
Full Load Current - Inductive
65 A
Number of Normally Open Main Contacts
3
Electrical Operating Durability
1,800,000, 500,000
Full Load Current - Resistive
80 A
Minimum Operating Temperature
-40 Degrees F
Maximum Voltage Rating
690V AC
Vibration Resistance
4 G (Contactor Closed), 2 G (Contactor Open)
Rated Short-Time Withstand Current
100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit), 520 A (at 40°C for 10 s Power Circuit), 900 A (at 40°C for 1 s Power Circuit), 110 A (at 40°C for 10 min Power Circuit), 260 A (at 40°C for 1 min Power Circuit)
Fuse Amps
10 A (Signalling Circuit), 125 A (Type 1 Power Circuit), 125 A (Type 2 Power Circuit)
Includes Protective Cover
Yes
Rated Making Capacity
140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit), 1000 A @ 440V (Power Circuit)
Rated Insulation Volts
690V
Application
Motor Control, Resistive Load
Environmental Attributes
Mercury Free, Pollution Degree 3
Overvoltage Category
CAT III
Electrical Connection
Control Circuit: Screw Clamp Terminals, Power Circuit: EverLink BTR Screw Connectors
Signalling Circuit Frequency
25 to 400 Hz
Operating Speed
3600 cycles per hr
Impulse Withstand Voltage
6 kV
Switching Current
5 mA (Signalling Circuit)
Max. Operating Watts
18.5 kW (at 220 to 230V AC 50 Hz), 30 kW (at 380 to 400V AC 50 Hz), 37 kW (at 415V AC 50 Hz), 37 kW (at 440V AC 50 Hz), 37 kW (at 500V AC 50 Hz), 37 kW (at 660 to 690V AC 50 Hz)
Thermal Amperage
10 A (at 60°C Signalling Circuit), 80 A (at 60°C Power Circuit)
Switching Voltage
17 V (Signalling Circuit)
Rated Breaking Capacity
1000 A @ 440V
Electrical Durability
1.8 Mcycles (57 A, AC-3, Less than 440 V); 0.5 Mcycles (80 A, AC-1, Less than 440 V)
Tightening Torque
1.7 Nm (Control Circuit), 5 to 8 Nm (Power Circuit)
Operating Time
55 to 65 ms (Closing), 20 to 120 ms (Opening)
Mechanical Durability
6 Mcycles
Features
Built-In Bi-Directional Peak Limiting; Preassembled with Reversing Power Busbar
Control Circuit Voltage Limits
Drop-Out AC/DC: Less Than 0.1 Uc (at -40 to 70°C); Operational AC/DC: 0.85 to 1.1 Uc (at -40 to 60°C), 1 to 1.1 Uc (at 60 to 70°C)
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Shock Resistance
15 G for 11 ms (Contactor Closed), 10 G for 11 ms (Contactor Open)