Key Features

  • Full Load Amps-Inductive 65 A
  • Action Non-Reversing
  • Full Load Amps-Resistive 80 A
  • Number of Poles 3
  • Reversing No
See all product information

Product Information

Dimensions

Height 4.8 in
Width 2.17 in
Depth 4.72 in
Working Height Up to 9842.52 ft
Overall Width 2.17 in
Overall Height 4.8 in
Overall Depth 4.72 in

Details

Item IEC Magnetic Contactor
Full Load Amps-Inductive 65 A
Action Non-Reversing
Full Load Amps-Resistive 80 A
Number of Poles 3
Coil Volts 120 V AC
Reversing No
HP @ 1 Phase - 230V 10
HP @ 1 Phase - 120V 5 hp
HP @ 1 Phase - 240V 10 hp
HP @ 3 Phase - 208V 20 hp
HP @ 3 Phase - 575V 50 hp
HP @ 3 Phase - 240V 20 hp
HP @ 3 Phase - 480V 40 hp
Enclosure NEMA Rating No Enclosure
Aux. Contact Configuration 1NO/1NC
Hz 50/60
Frame / Series / Class / Code TeSys
Standards CCC, CSA, CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, GOST, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, UL 508, UL Listed
Auxiliary Contact Form 1NO/1NC
Includes Everlink Power Connections
Series TeSys Deca
Hold VA 13 VA
Operating Time 4 to 19 ms (Opening), 12 to 26 ms (Closing)
Switching Voltage 17 V (Signalling Circuit)
Watts Loss 4 to 5W
Tightening Torque 1.7 Nm (Control Circuit), 2.5 to 8 Nm (Power Circuit)
Max. Temperature 850°C
Rated Making Capacity 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit), 1000 A @ 440V (Power Circuit)
Control Circuit Voltage Limits Drop-Out AC: 0.3 to 0.6 Uc (at -40 to 70°C 60 Hz) , Operational AC: 0.85 to 1.1 Uc (at -40 to 60°C 60 Hz), 1 to 1.1 Uc (at 60 to 70°C 60 Hz)
Includes Protective Cover Yes
Mechanical Durability 6 Mcycles
Electrical Durability 1.4 Mcycles (80 A, AC-1, Less than 440 V); 1.45 Mcycles (65 A, AC-3, Less than 440 V); 1.45 Mcycles (65 A, AC-3e, Less than 440 V)
Inrush VA 140 VA
Mounts On Plate, Rail
IP Rating IP20
Rated Breaking Capacity 1000 A @ 440V
Non-Overlap Time 1.5 ms
Signalling Circuit Frequency 25 to 400 Hz
Impulse Withstand Voltage 6 kV
Environmental Attributes Mercury Free, PVC Free, Toxic Heavy Metal Free, Pollution Degree 3
Application Motor Control, Resistive Load
Impedance 1.5 mOhm
Rated Voltage 690V AC, 300V DC
Overvoltage Category CAT III
Net Weight 0.86 kg
Operating Speed 3600 cycles per hr
Features Without Built-In Suppressor Module
Rated Short-Time Withstand Current 520 A (at 40°C for 10 s Power Circuit), 900 A (at 40°C for 1 s Power Circuit), 110 A (at 40°C for 10 min Power Circuit), 260 A (at 40°C for 1 min Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit)
Fuse Amps 10 A (Signalling Circuit), 125 A (Type 1 Power Circuit), 125 A (Type 2 Power Circuit)
Max. Operating Watts 11 kW (at 400V AC 50/60 Hz AC-4), 18.5 kW (at 220 to 230V AC 50/60 Hz AC-3), 30 kW (at 380 to 400V AC 50/60 Hz AC-3), 37 kW (at 500V AC 50/60 Hz AC-3), 37 kW (at 660 to 690V AC 50/60 Hz AC-3), 18.5 kW (at 220 to 230V AC 50/60 Hz AC-3e), 30 kW (at 380 to 400V AC 50/60 Hz AC-3e), 37 kW (at 500V AC 50/60 Hz AC-3e), 37 kW (at 660 to 690V AC 50/60 Hz AC-3e)
Switching Current 5 mA (Signalling Circuit)
Shock Resistance 10 G for 11 ms (Contactor Open), 15 G for 11 ms (Contactor Closed)
Fire Rating UL 94 V1
Thermal Amperage 10 A (at 60°C Signalling Circuit), 80 A (at 60°C Power Circuit)
Insulation Resistance Range Greater Than 10 MOhms (Signalling Circuit)
Vibration Resistance 4 G (Contactor Closed), 2 G (Contactor Open)
Rated Insulation Volts 600/690V
Electrical Connection Screw Clamp Terminals
Mounting Style DIN Rail, Plate
Includes Auxiliary Contacts Yes
Horsepower @ Single Phase - 120V AC 5 hp
Horsepower @ Three Phase - 208V AC 20 hp
Maximum Operating Temperature 140 Degrees F
Horsepower @ Single Phase - 240V AC 10 hp
Coil Voltage 120V AC
Frequency 50/60 Hz
Resistance Properties Fire Resistant, Insulation Resistant
Reversing Capability Non-Reversing
NEMA Enclosure Rating No Enclosure
Contactor Style IEC
Phase Three
Full Load Current - Inductive 65 A
Full Load Current - Resistive 80 A
Terminal Connection Type Screw Clamp Terminals
Horsepower @ Three Phase - 600V AC 50 hp
Minimum Operating Temperature -40 Degrees F
Horsepower @ Three Phase - 240V AC 20 hp
Number of Auxillary Contacts 2
Maximum Voltage Rating 690V AC
Horsepower @ Three Phase - 480V AC 40 hp
Number of Normally Open Main Contacts 3
Electrical Operating Durability 1,400,000, 1,450,000
Mechanical Operating Durability 6,000,000
Embedded Surge Suppressor No

Description

IEC Magnetic Contactor, Auxiliary Contact Form 1NO/1NC, NEMA Enclosure Rating No Enclosure, NEMA Size Not Applicable, Coil Voltage 120V AC, Number of Poles 3, Full Load Current - Inductive 65 A, Full Load Current - Resistive 80 A, Reversing Capability Non-Reversing, Overall Height 4.8 in, Overall Width 2.17 in, Terminal Connection Type Screw Clamp Terminals, Mounting Style DIN Rail, Plate, Series TeSys Deca, Number of Auxillary Contacts 2, Contactor Style IEC

Ratings & Reviews

3 Reasons You Can Count On Us

  • Supplies for every job.

    Supplies for every job.

    10 million items and the exact one you need.

  • When you need it fast, count on Zoro!

    When you need it fast, count on Zoro!

    2 million products ship in 1 day.

  • Stretch your budget further.

    Stretch your budget further.

    Everyday low prices on the brands you love.