Auxiliary Contact Form
1NC/4NO
Minimum Overload Relay Current Setting
0.40 A
Maximum Overload Relay Current Setting
8:00 AM
Maximum Voltage Rating
690V AC
Standards
CCC, CSA C22.2 No 14, EN 60947-4-1, IACSE10, IEC 60947-4-1, nABS, nATEX, nBV, nC-tick, nCSA, nDNV, nEAC, nGL, nKERI, nLROS, nNOM, nRINA, nRMRoS, nUL, UL 508
Interface
Ethernet/IP, Modbus/TCP
For Use With
Short Circuit Protection And A Contactor
Number of Normally Open Contacts
4
Number of Contacts Included
5
Number of Normally Closed Contacts
1
Minimum Current Rating
0.4 A
Maximum Current Rating
8 A
Compatible with Series
TeSys T
Product Or Component Type
motor controller
Operating Altitude
<= 6561.68 ft (2000 m) without derating
Product Certifications
CCC || ABS || C-tick || NOM || CSA || RMRoS || RINA || UL || BV || KERI || DNV || GL || EAC || LROS (Lloyds register of shipping) || ATEX
Communication Port Protocol
Modbus TCP/EtherNet/IP
Short-Circuit Withstand
100 kA conforming to EN/IEC 60947-4-1
Current State 1 Guaranteed
logic input < 15 V 2 to 15 mA 15 ms
Contact Type and Composition
1 NO + 1 NC fault signal; 3 NO
Measurement Current
0.4-8 A
Metering Type
average current Iavg || temperature || earth-fault current || phase current I1, I2, I3 RMS || imbalance current
Bus Type
Ethernet IEEE 802.3 0 to 159 10 to 100 Mbit/s, RJ45 2 shielded twisted pairs
Measurement Accuracy
5 to 15 % earth fault current internal measurement || 1 % voltage 100 to 830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power
Permissible Power
480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
Protection Type
phase failure || locked rotor || earth-leakage protection || thermal protection || overload || phase unbalance || reverse polarity protection || power factor variation || overload (long time) || thermal overload protection || load fluctuation
Rated Impulse Withstand Voltage
6 kV current or voltage measurement circuit EN/IEC 60947-4-1; 0.8 kV communication circuit EN/IEC 60947-4-1; 0.8 kV supply, inputs and outputs EN/IEC 60947-4-1
Load Current
5 A 250 V AC logic output || 5 A 30 V DC logic output
Connections - Terminals
control circuit connector 1 0.25-2.5 mm² AWG 24 to AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24 to AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24 to AWG 14)flexible without cable end || control circuit connector 1 0.2-2.5 mm² AWG 24 to AWG 14)solid without cable end || control circuit connector 2 0.2-1 mm² AWG 24 to AWG 14)flexible with cable end || control circuit connector 2 0.2-1.5 mm² AWG 24 to AWG 14)flexible without cable end || control circuit connector 2 0.5-1.5 mm² AWG 24 to AWG 14)flexible without cable end || control circuit connector 2 0.2-1 mm² AWG 24 to AWG 14)solid without cable end
Supply Voltage Limits
20.4-26.24 V DC
Associated Fuse Rating
4 A gG output || 0.5 A gG control circuit
Fire Resistance
650°C EN/IEC 60695-2-12 || 960°C UL 94
Rated Insulation Voltage
690 V EN/IEC 60947-1; 690 V CSA C22.2 No 14; 690 V UL 508
Network And Machine Diagnosis Type
event recording || remaining operating time before overload tripping || trip context information || waiting time after overload tripping || running hours counter/operating time || trip history information || fault recording || starting current and time || phase fault and earth fault trip counters || motor control command recording
Current Consumption
56 to 127 mA
Maximum Operating Frequency
2 Hz
Mechanical Robustness
vibrations mounted on symmetrical rail1 Gn, 5 to 300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5 to 300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
Maximum Operating Rate
1800 cyc/h
Ambient Air Temperature For Operation
-20-60°C
Protective Treatment
12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
Tightening Torque
control circuit 0.5-0.6 N.m flat 3 mm
Current State 0 Guaranteed
logic input < 5 V <= 15 mA 5 ms
Electromagnetic Compatibility
electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 || radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 || fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 || voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 || conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 || temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 || temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Ambient Air Temperature For Storage
-40-80°C
Relay Application
equipment monitoring and control