- Item
- Motor Controller
- Auxiliary Contact Form
- 1NC/4NO
- Minimum Overload Relay Current Setting
- 0.40 A
- Maximum Overload Relay Current Setting
- 8:00 AM
- Overload Protection Type
- Thermal
- Maximum Voltage Rating
- 690V AC
- Standards
- ATEX Compliant, CSA C22.2 No 14, EN 60947-4-1, IACSE10, IEC 60947-4-1, nABS, nBV, nC-tick, nCCC, nCSA, nDNV, nEAC, nGL, nKERI, nLROS, nNOM, nRINA, nRMRoS, nUL, UL 508
- Interface
- Profibus DP
- Control Voltage
- 24V DC
- For Use With
- Short Circuit Protection And A Contactor
- Minimum Current Rating
- 0.4 A
- Maximum Current Rating
- 8 A
- Number of Normally Open Contacts
- 4
- Number of Contacts Included
- 5
- Compatible with Series
- TeSys T
- Number of Normally Closed Contacts
- 1
- Overvoltage Category
- III
- Communication Port Protocol
- Profibus DP
- Tightening Torque
- control circuit 0.5-0.6 N.m flat 3 mm
- Ambient Air Temperature For Storage
- -40-80°C
- Logic Input Number
- 6
- Metering Type
- earth-fault current || average current Iavg || imbalance current || phase current I1, I2, I3 RMS || temperature
- Fire Resistance
- 650°C EN/IEC 60695-2-12 || 960°C UL 94
- Current State 1 Guaranteed
- logic input < 15 V 2 to 15 mA 15 ms
- Network And Machine Diagnosis Type
motor control command recording || running hours counter/operating time || trip history information || fault recording || starting current and time || phase fault and earth fault trip counters || remaining operating time before overload tripping || waiting time after overload tripping || trip context information || event recording
- Operating Altitude
- <= 6561.68 ft (2000 m) without derating
- Bus Type
- Profibus DP polarised 2-wire RS485 1 to 125 9.6 kbit/s to 12 Mbit/s, SUB-D 9 2 shielded twisted pairs, type A || Profibus DP polarised 2-wire RS485 1 to 125 9.6 kbit/s to 12 Mbit/s, terminal block 2 shielded twisted pairs, type A
- Pollution Degree
- 3
- Connections - Terminals
control circuit connector 1 0.25-2.5 mm² AWG 24 to AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24 to AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24 to AWG 14)flexible without cable end || control circuit connector 1 0.2-2.5 mm² AWG 24 to AWG 14)solid without cable end || control circuit connector 2 0.2-1 mm² AWG 24 to AWG 14)flexible with cable end || control circuit connector 2 0.2-1.5 mm² AWG 24 to AWG 14)flexible without cable end || control circuit connector 2 0.5-1.5 mm² AWG 24 to AWG 14)flexible without cable end || control circuit connector 2 0.2-1 mm² AWG 24 to AWG 14)solid without cable end
- Permissible Power
- 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
- Current State 0 Guaranteed
- logic input < 5 V <= 15 mA 5 ms
- Device Short Name
- LTMR
- Measurement Accuracy
- 5 to 15 % earth fault current internal measurement || 1 % voltage 100 to 830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power
- Electromagnetic Compatibility
electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 || radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 || fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 || voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 || conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 || temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 || temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
- Supply Voltage Limits
- 20.4-26.24 V DC
- Connection Pitch
- 5.08 mm
- Measurement Current
- 0.4-8 A
- Product Or Component Type
- motor controller
- Web Services
- web server
- Associated Fuse Rating
- 4 A gG output || 0.5 A gG control circuit
- Ambient Air Temperature For Operation
- -20-60°C
- Mechanical Robustness
- vibrations mounted on symmetrical rail1 Gn, 5 to 300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5 to 300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
- Protective Treatment
- 12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
- Protection Type
- thermal protection || load fluctuation || power factor variation || phase failure || overload || reverse polarity protection || overload (long time) || earth-leakage protection || locked rotor || thermal overload protection || phase unbalance
- Contacts Type And Composition
- 1 NO + 1 NC fault signal || 3 NO
- Input Current
- 7 mA
- Load Current
- 5 A 250 V AC logic output || 5 A 30 V DC logic output
- Product Certifications
- ATEX || GL || LROS (Lloyds register of shipping) || CSA || UL || C-tick || CCC || DNV || RINA || ABS || KERI || EAC || BV || NOM || RMRoS
- Range
- TeSys
- Short-Circuit Withstand
- 100 kA conforming to EN/IEC 60947-4-1
- Maximum Operating Rate
- 1800 cyc/h
- Maximum Operating Frequency
- 2 Hz
- Current Consumption
- 56 to 127 mA
- Compatibility Code
- LTMR
- Product Name
- TeSys T
- IP Rating
- IP20
- Rated Insulation Voltage
- 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
- Relay Application
- equipment monitoring and control