CSA C22.2 No 14, EN 60947-4-1, IACSE10, IEC 60947-4-1, nABS, nATEX, nBV, nC-tick, nCCC, nCSA, nDNV, nEAC, nGL, nKERI, nLROS, nNOM, nRINA, nUL, RMRoS, UL 508
Interface
Modbus
For Use With
Short Circuit Protection And A Contactor
Web Services
web server
Bus Type
Modbus 2-wire RS 485 1 to 247 1.2 to 19.2 kbit/s, RJ45 2 shielded twisted pairs || Modbus 2-wire RS 485 1 to 247 1.2 to 19.2 kbit/s, terminal block 2 shielded twisted pairs
Protective Treatment
12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
Supply Voltage Limits
93.5-264 V AC
Product Name
TeSys T
Input Current
3.1 mA 100 V || 7.5 mA 240 V
Network And Machine Diagnosis Type
fault recording || starting current and time || remaining operating time before overload tripping || waiting time after overload tripping || motor control command recording || event recording || trip history information || running hours counter/operating time || phase fault and earth fault trip counters || trip context information
Tightening Torque
control circuit 0.5-0.6 N.m flat 3 mm
Current State 0 Guaranteed
logic input 0 to 40 V <= 15 mA 25 ms
Ambient Air Temperature For Storage
-40-80°C
Current State 1 Guaranteed
logic input 79 to 264 V >= 2 mA 25 ms
Logic Input Number
6
Device Short Name
LTMR
Compatibility Code
LTMR
Load Current
5 A 250 V AC logic output || 5 A 30 V DC logic output
Associated Fuse Rating
4 A gG output || 0.5 A gG control circuit
Connections - Terminals
control circuit connector 1 0.25-2.5 mm² AWG 24 to AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24 to AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24 to AWG 14)flexible without cable end || control circuit connector 1 0.2-2.5 mm² AWG 24 to AWG 14)solid without cable end || control circuit connector 2 0.2-1 mm² AWG 24 to AWG 14)flexible with cable end || control circuit connector 2 0.2-1.5 mm² AWG 24 to AWG 14)flexible without cable end || control circuit connector 2 0.5-1.5 mm² AWG 24 to AWG 14)flexible without cable end || control circuit connector 2 0.2-1 mm² AWG 24 to AWG 14)solid without cable end
Permissible Power
480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
Current Consumption
8 to 62.8 mA
Fire Resistance
650°C EN/IEC 60695-2-12 || 960°C UL 94
Metering Type
temperature || phase current I1, I2, I3 RMS || average current Iavg || earth-fault current || imbalance current
Measurement Accuracy
5 to 15 % earth fault current internal measurement || 1 % voltage 100 to 830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power
Maximum Operating Frequency
2 Hz
Product Or Component Type
motor controller
Mechanical Robustness
vibrations mounted on symmetrical rail1 Gn, 5 to 300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5 to 300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 || fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 || voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 || conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 || temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 || temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Maximum Operating Rate
1800 cyc/h
Communication Port Protocol
Modbus
Ambient Air Temperature For Operation
-20-60°C
Minimum Current Rating
1.35 A
Number of Contacts Included
5
Number of Normally Closed Contacts
1
Maximum Current Rating
27 A
Number of Normally Open Contacts
4
Compatible with Series
TeSys T
Relay Application
equipment monitoring and control
IP Rating
IP20
Rated Insulation Voltage
690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
Description
Motor Management System, Number of Normally Open Contacts 4, Number of Normally Closed Contacts 1, Number of Contacts Included 5, Operating Voltage 690V AC, Control Voltage 100-240V AC, Interface Modbus, Compatible with Series TeSys T, Overall Width 3.58 in, Standards CSA C22.2 No 14, EN 60947-4-1, IACSE10, IEC 60947-4-1, nABS, nATEX, nBV, nC-tick, nCCC, nCSA, nDNV, nEAC, nGL, nKERI, nLROS, nNOM, nRINA, nUL, RMRoS, UL 508, Overall Height 2.4 in, Overall Depth 4.82 in, Maximum Current Rating 27 A