NEMA Magnetic Motor Starter, Non-Reversing, 1NO, 240V AC, 3 P, Screw

  • Mfr # 14FUF32BG
  • Zoro # G2214737
product price: 
$
887.99
/ea
Free Shipping & Returns

Key Features

Auxiliary Contact Form
1NO
Coil Voltage
190-220/220-240V AC
Number of Poles
3
Full Load Current - Inductive
52 A
Reversing Capability
Non-Reversing
See all product information
Unlock 30-day payment terms
Unlock 30-day payment terms
Business customers can apply for Net 30—no fees, no interest, fast approval. Terms apply.
Create Account
Get 10% off your order
Get 10% off your order
Sign up for our email list and receive your promo code via email.

Specifications

Details

MFR #
14FUF32BG
Zoro #
G2214737
UPC #
040892541052
Country of Origin
United States
Item
NEMA Magnetic Motor Starter
Auxiliary Contact Form
1NO
Coil Voltage
190-220/220-240V AC
Number of Poles
3
Full Load Current - Inductive
52 A
Reversing Capability
Non-Reversing
Terminal Connection Type
Screw
Number of Auxillary Contacts
1
Standards
CSA 22.2 No.14, NEMA ICS 2, UL 508
HP @ 3 Phase - 575V
25 hp
Maximum Overload Relay Current Setting
52 A
Auxiliary Contact Module Capacity
7
Series
FVNR
Phase
Three
Horsepower @ Three Phase - 600V AC
25 hp
Maximum Voltage Rating
600V AC
Mounting Style
Surface
Minimum Operating Temperature
-4 Degrees F
Frequency
50/60 Hz
Mechanical Operating Durability
10,000,000
Trip Class
5/10/20/30
Overload Protection Type
Electronic
Includes Auxiliary Contacts
Yes
Maximum Operating Temperature
104 Degrees F
Starter Style
NEMA
Horsepower @ Three Phase - 208V AC
10 hp
Horsepower @ Three Phase - 240V AC
15 hp
Minimum Overload Relay Current Setting
13 A
Response Time
10 to 24 msec (OFF-Delay Time), 19 to 29 msec (ON-Delay Time)
NEMA Enclosure Rating
1
Mounting Postion
Vertical
Current AC
45 A
Horsepower @ Three Phase - 480V AC
25 hp

Dimensions

NEMA Size
2
Overall Width
8 in
Overall Height
14 in
Overall Depth
7 in

Description

NEMA Magnetic Motor Starter, Includes Auxiliary Contacts Yes, Maximum Overload Relay Current Setting 52 A, Overload Protection Type Electronic, Minimum Overload Relay Current Setting 13 A, Trip Class 5/10/20/30, Series FVNR, Number of Poles 3, Number of Auxillary Contacts 1, Phase Three, Mounting Style Surface, Auxiliary Contact Form 1NO, Starter Style NEMA, Reversing Capability Non-Reversing, Maximum Voltage Rating 600V AC, Coil Voltage 190-220/220-240V AC

Restrictions

WARNING: Reproductive Harm For more information go to www.P65Warnings.ca.gov

Ratings & reviews