Item
|
IEC Magnetic Contactor
|
Full Load Amps-Inductive
|
115 A
|
Full Load Amps-Resistive
|
200 A
|
Action
|
Non-Reversing
|
Number of Poles
|
3
|
Coil Volts
|
240 V AC
|
Reversing
|
No
|
HP @ 3 Phase - 208V
|
30 hp
|
HP @ 3 Phase - 575V
|
100 hp
|
HP @ 3 Phase - 240V
|
40 hp
|
HP @ 3 Phase - 480V
|
75 hp
|
Enclosure NEMA Rating
|
No Enclosure
|
Aux. Contact Configuration
|
1NO/1NC
|
Hz
|
50/60
|
Standards
|
BV, CCC, CSA, CSA C22.2 No 14, DNV, EN 60947-4-1, EN 60947-5-1, GL, GOST, IEC 60947-4-1, IEC 60947-5-1, LROS, RINA, UKCA, UL 508, UL Listed
|
Auxiliary Contact Form
|
1NO/1NC
|
Series
|
TeSys Deca
|
Shock Resistance
|
15 G for 11 ms (Contactor Closed), 6 G for 11 ms (Contactor Open)
|
Max. Temperature
|
850°C
|
Mechanical Durability
|
8 Mcycles
|
Operating Speed
|
2400 cycles per hr
|
Thermal Amperage
|
200 A (at 60°C Power Circuit)
|
Inrush VA
|
280 to 350 VA
|
Features
|
Built-In Bi-Directional Peak Limiting Diode Suppressor
|
Vibration Resistance
|
4 G (Contactor Closed), 2 G (Contactor Open)
|
Electrical Connection
|
Screw Clamp Terminals
|
Tightening Torque
|
1.2 Nm (Control Circuit), 12 Nm (Power Circuit)
|
Hold VA
|
2 to 18 VA
|
Fire Rating
|
UL 94 V1
|
Switching Current
|
5 mA (Signalling Circuit)
|
Impedance
|
0.6 mOhm
|
Operating Time
|
6 to 20 ms (Opening), 20 to 50 ms (Closing)
|
Control Circuit Voltage Limits
|
Drop-Out AC: 0.3 to 0.5 Uc (at -40 to 70°C 50/60 Hz); Operational AC: 0.8 to 1.15 Uc (at -40-55°C 50/60 Hz), 1 to 1.15 Uc (at 55-70°C 50/60 Hz)
|
Rated Short-Time Withstand Current
|
250 A (at 40°C for 10 min Power Circuit), 550 A (at 40°C for 1 min Power Circuit), 950 A (at 40°C for 10 s Power Circuit), 1100 A (at 40°C for 1 s Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit)
|
Environmental Attributes
|
Mercury Free, PVC Free, Pollution Degree 3
|
Electrical Durability
|
0.8 Mcycles (200 A, AC-1, Less than 440 V); 0.95 Mcycles (115 A, AC-3, Less than 440 V); 0.95 Mcycles (115 A, AC-3e, Less than 440 V)
|
Rated Voltage
|
1000V AC, 300V DC
|
Net Weight
|
2.5 kg
|
Overvoltage Category
|
CAT III
|
IP Rating
|
IP20
|
Rated Breaking Capacity
|
1100 A @ 440V
|
Max. Operating Watts
|
30 kW (at 220 to 230V AC 50/60 Hz AC-3), 55 kW (at 380 to 400V AC 50/60 Hz AC-3), 59 kW 415 to (at 440V AC 50/60 Hz AC-3), 75 kW (at 500V AC 50/60 Hz AC-3), 80 kW (at 660 to 690V AC 50/60 Hz AC-3), 65 kW (at 1000V AC 50/60 Hz AC-3), 18.5 kW (at 400V AC 50/60 Hz AC-4), 30 kW (at 220 to 230V AC 50/60 Hz AC-3e), 55 kW (at 380 to 400V AC 50/60 Hz AC-3e), 59 kW 415 to (at 440V AC 50/60 Hz AC-3e), 75 kW (at 500V AC 50/60 Hz AC-3e), 80 kW (at 660 to 690V AC 50/60 Hz AC-3e), 65 kW (at 1000V AC 50/60 Hz AC-3e)
|
Rated Insulation Volts
|
600/1000V (Power Circuit), 600/690V (Signalling Circuit)
|
Includes Protective Cover
|
Yes
|
Watts Loss
|
3 to 8W
|
Insulation Resistance Range
|
Greater Than 10 MOhms (Signalling Circuit)
|
Application
|
Motor Control, Resistive Load
|
Switching Voltage
|
17 V (Signalling Circuit)
|
Fuse Amps
|
250 A (Type 1 Power Circuit), 200 A (Type 2 Power Circuit), 10 A (Signalling Circuit)
|
Signalling Circuit Frequency
|
25 to 400 Hz
|
Rated Making Capacity
|
1260 A @ 440V (Power Circuit), 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit)
|
Mounts On
|
Plate, Rail
|
Impulse Withstand Voltage
|
8 kV
|
Non-Overlap Time
|
1.5 ms
|
Horsepower @ Three Phase - 600V AC
|
100 hp
|
Horsepower @ Single Phase - 240V AC
|
2 hp
|
Mechanical Operating Durability
|
8,000,000
|
Number of Normally Open Main Contacts
|
3
|
Mounting Style
|
DIN Rail, Plate
|
Number of Auxillary Contacts
|
2
|
Coil Voltage
|
240V AC
|
NEMA Enclosure Rating
|
No Enclosure
|
Maximum Voltage Rating
|
1000V AC
|
Embedded Surge Suppressor
|
Yes
|
Phase
|
Three
|
Resistance Properties
|
Fire Resistant, Insulation Resistant
|
Horsepower @ Three Phase - 240V AC
|
40 hp
|
Frequency
|
50/60 Hz
|
Contactor Style
|
IEC
|
Reversing Capability
|
Non-Reversing
|
Maximum Operating Temperature
|
140 Degrees F
|
Electrical Operating Durability
|
800,000, 950,000
|
Horsepower @ Three Phase - 208V AC
|
30 hp
|
Full Load Current - Resistive
|
200 A
|
Horsepower @ Three Phase - 480V AC
|
75 hp
|
Minimum Operating Temperature
|
-40 Degrees F
|
Full Load Current - Inductive
|
115 A
|
Includes Auxiliary Contacts
|
Yes
|
Terminal Connection Type
|
Screw Clamp Terminals
|