Item
IEC Miniature Magnetic Contactor
Auxiliary Contact Form
1NC
Reversing Capability
Reversing
Terminal Connection Type
Screw Clamp
Number of Auxillary Contacts
1
Standards
BS 5424, CSA, IEC 60947, NF C 63-110, UKCA, UL Listed, VDE 0660
HP @ 3 Phase - 575V
10 hp
HP @ 1 Phase - 230V
1-1/2
Enclosure NEMA Rating
No Enclosure
Application
Motor Control, Resistive Load
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Shock Resistance
10 G for 11 ms (on X axis with Contactor Closed), 15 G for 11 ms (on Y and Z axis with Contactor Closed), 6 G for 11 ms (on X axis with Contactor Open), 10 G for 11 ms (on Y and Z axis with Contactor Open)
Operating Speed
3600 cycles per hr
Signalling Circuit Frequency
Less Than 400 Hz
Control Circuit Voltage Limits
Operational: 0.8 to 1.15 Uc (at 50°C), Drop-Out: 0.2 to 0.75 Uc (at 50°C)
Max. Operating Watts
4 kW (at 480V AC 50/60 Hz), 4 kW (at 500 to 600V AC 50/60 Hz), 4 kW (at 660 to 690V AC 50/60 Hz), 3 kW (at 220 to 230V AC 50/60 Hz), 5.5 kW (at 380 to 415VAC 50/60 Hz), 5.5 kW (at 440V AC 50/60 Hz)
Electrical Durability
0.3 Mcycles (20 A, AC-1, Less than 440 V); 1.3 Mcycles (12 A, AC-3, Less than 440 V); 1.3 Mcycles (12 A, AC-3e, Less than 440 V)
Rated Short-Time Withstand Current
115 A (at 50°C for 1 s Power Circuit), 105 A (at 50°C for 5 s Power Circuit), 100 A (at 50°C for 10 s Power Circuit), 75 A (at 50°C for 30 s Power Circuit), 55 A (at 50°C for 1 min Power Circuit), 50 A (at 50°C for 3 min Power Circuit), 80 A (For 1 s Signalling Circuit), 90 A (For 500 ms Signalling Circuit), 110 A (For 100 ms Signalling Circuit), 25 A (at 50°C for 15 min Power Circuit)
Switching Current
5 mA (Signalling Circuit)
Impulse Withstand Voltage
8 kV
Rated Breaking Capacity
110 A @ 440V, 80 A @ 500V, 70 A @ 660 to 690V
Mechanical Durability
5 Mcycles
Tightening Torque
0.8 to 1.3 Nm
Environmental Attributes
Mercury Free, Toxic Heavy Metal Free
Switching Voltage
17 V (Signalling Circuit)
Rated Insulation Volts
600/690V
Overvoltage Category
CAT III
Features
Preassembled with Reversing Power Busbar
Rated Making Capacity
144 A @ 690V (AC Power Circuit), 110 A (AC Signalling Circuit)
Operating Time
10 to 20 ms (Coil Energisation and NO Closing), 10 to 20 ms (Coil De-Energisation and NO Opening)
Fire Rating
UL 94 V1, NF F 16-101, NF F 16-102
Fuse Amps
25 A (Power Circuit), 10 A (Signalling Circuit)
Vibration Resistance
4 G (Contactor Closed), 2 G (Contactor Open)
Electrical Operating Durability
1,300,000, 300,000
Maximum Operating Temperature
122 Degrees F
NEMA Enclosure Rating
No Enclosure
Horsepower @ Single Phase - 240V AC
1 1/2 hp
Horsepower @ Single Phase - 120V AC
1/2 hp
Mechanical Operating Durability
5,000,000
Horsepower @ Three Phase - 240V AC
3 hp
Mounting Style
DIN Rail, Plate
Includes Auxiliary Contacts
Yes
Full Load Current - Inductive
12:00 AM
Horsepower @ Three Phase - 480V AC
7 1/2 hp
Minimum Operating Temperature
-13 Degrees F
Embedded Surge Suppressor
No
Horsepower @ Three Phase - 600V AC
10 hp
Full Load Current - Resistive
20 A
Number of Normally Open Main Contacts
3
Maximum Voltage Rating
690V AC
Resistance Properties
Insulation Resistant
Ambient Air Temperature For Operation
-13 to 122°F (-25 to 50°C)
Protective Treatment
TC IEC 60068; TC DIN 50016
Rated Operational Voltage
Power circuit 690 V AC 50/60 Hz; Signalling circuit Less than or Equal to 690 V AC 50/60 Hz
Contactor Application
Resistive load; Motor control
Ambient Air Temperature For Storage
-58 to 176°F (-50 to 80°C)
Control Circuit Type
AC 50/60 Hz
Utilisation Category
AC-3; AC-3e; AC-4; AC-1
Inrush Power in VA
30 VA (at 68°F (20°C))
Device Application
Control
Interlocking Type
Mechanical
Rated Operational Current
12 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-3 for power circuit; 12 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-3e for power circuit; 20 A (at Less than 140°F (60°C)) at Less than or Equal to 690 V AC AC-1 for power circuit
Auxiliary Contacts Type
Instantaneous 1 NC
Operating Altitude
6561.68 ft (2000 m) without derating
Non Overlap Distance
0.02 in (0.5 mm)
Maximum Operating Rate
3600 cyc/h
Control Circuit Voltage
24 V AC 50/60 Hz
Conventional Free Air Thermal Current
20 A (at 140°F (60°C)) for power circuit; 10 A (at 122°F (50°C)) for signalling circuit
Mechanical Robustness
Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27; Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27; Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27; Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27; Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27; Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27; Vibrations contactor closed4 Gn, 5 to 300 Hz IEC 60068-2-6; Vibrations contactor opened2 Gn, 5 to 300 Hz IEC 60068-2-6
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pole Contact Composition
3 NO