UPS Type
Line Interactive
Output Voltage
110/115/120V
Backup Time (Half/Full Load)
17.70 min/6.50 min
Transfer Time
5 milliseconds (AC to battery), 1 milliseconds (Battery to AC)
Standards
UL Listed Certification
NEMA Receptacle Configuration
(8) 5-15R
NEMA Plug Configuration
5-15P
Battery Mode BTU / Hr. (Full Load)
650
Cold Start (Startup in Battery Mode During a Power Failure)
Cold-start operation supported
Installation Form Factors Supported with Included Accessories
2 post 19 inch rackmount; 4 post 19 inch rackmount
Output Volt Amp Capacity (VA)
1500
Relative Humidity
0 to 95%, non-condensing
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
Output Watt Capacity (Watts)
1000
Battery Access
Front panel battery access door
Communications Interface
DB9 Serial; EPO (emergency power off); USB
AC Mode BTU / Hr. (Full Load)
223
AC Mode Efficiency Rating (100% Load)
0.94
UPS AC Suppression Joule Rating
570
Undervoltage Correction
Input voltages between 83 and 107 are boosted by 14%
Internal UPS Replacement Battery Cartridge
RBC93-2U
Individually Controllable Load Banks
No
Communications Cable
USB cabling included
High Availability UPS Features
Hot swappable batteries
Alarm Cancel Operation
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
Operating Elevation (m)
0 - 3000 m
Front Panel LCD Display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
UPS Certifications
Meets FCC Part 15 Category A (EMI); Tested to CSA (Canada); Tested to NOM (Mexico); Tested to UL1778 (USA)
UPS AC Suppression Response Time
Instantaneous
Installation Form Factors Supported with Optional Accessories
4 post rackmount full-depth ( 4POSTRAILKIT ); Tower ( 2-9USTAND ); Wallmount ( 2POSTRMKITWM )
Rated input current (Maximum Load)
12A
Full Load Runtime (min.)
6.5 min. (1000w)
Overvoltage Correction
Input voltages between 128 and 147 are reduced by 12%
Grounding Lug
Back panel grounding lug
Primary Form Factor
Rackmount
Operating Elevation (ft.)
0-3000M (0-10,000 Ft)
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Nominal Input Voltage(s) Supported
120V AC
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
DC System Voltage (VDC)
36
Output kVA Capacity (kVA)
1.5
Audible Noise
45 dBA maximum, front side 1m
Network UPS Tools Compatibility
NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at http://www.networkupstools.org/stable-hcl.html?manufacturer=Tripp Lite
Output kW Capacity (kW)
1
Output Voltage Regulation (Battery Mode)
+/- 5%
Switches
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
Battery Recharge Rate (Included Batteries)
Less than 4.5 hours from 10% to 90% (typical, full load discharge)
Voltage Regulation Description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 147
High Voltage Transfer to Battery Power (Setpoint)
147
Battery Replacement Description
Hot-swappable, user replaceable batteries
EMI / RFI AC Noise Suppression
Yes
Network Monitoring Port Description
Supports detailed monitoring of UPS and site power conditions
Audible Alarm
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
Input Circuit Breakers
15A
Low Voltage Transfer to Battery Power (Setpoint)
83
Included Mounting Accessory Description
Includes UPSHDEARKIT for 2 point front-mount and 2 point center-mount rackmount installation in 2 and 4 post racks, plus wallmount installation; For additional stability in 4 post racks, consider optional 4 post mounting accessories 4POSTRAILKIT and 4POSTRAILKITWM
Output AC Waveform (Battery Mode)
Pure Sine wave
Half Load Runtime (min.)
17.7 min. (500w)
Output Voltage Regulation (Line Mode)
-21%, +8%
Nominal Output Voltage(s) Supported
110V; 115V; 120V
PowerAlert Software
For local monitoring via the UPS™s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
Recommended Electrical Service
15A 120V
Thermal Dissipation
65.35 W
Battery Management
user-replaceable
Surge Energy Rating
570 J
Alarm
Low Battery, UPS StartUp, Power Failure, Remote Shutdown, UPS Fault, Overload
Load Capacity
1500 VA/1000 W
Maximum Operating Temperature
104°F (40°C)
Waveform Type
Pure Sine Wave, Sine Wave
Protection Type
EMI / RFI, Brownout, Black Out, Under Voltage, Surge, Over Voltage
Package Contents
SMC15002URM UPS System, USB Cable, 2 & 4 Post Rackmount Installation Hardware, Instruction Manual
Sound Emission (A-Weighted)
45 dB(A)
Package Includes
SMC15002URM SmartPro 120V 1.5kVA 1kW Line-Interactive Sine Wave UPS;USB cable;UPSHDEARKIT mounting hardware;Owner's manual
UPS Applications
Audio/Video; Large Network; High-End Desktop/Small Network; Retail/Point of Sale; Hospitality
Product Compliance
FCC Part 15 Class A (USA)
Grounding Details
Back panel grounding lug
Output Capacity (VA)
1500
Product Certifications
CSA (Canada); NOM (Mexico); UL 1778
Output Capacity (Watts)
1000