- MFR #
- SR2PACKBD
- Zoro #
- G0862550
- UPC #
- 785901693857
- Country of Origin
- Korea, Republic of
- Item
- Compact Discovery Pack
- Features
FBD Programming Control Scheme Lines, (8) Resistive Discrete Inputs with Voltage of 24V DC, IP Degree of Protection: IP20, IP Degree of Protection: IP40, Rated Supply Voltage of 24V DC, (4) Analogue Inputs with Voltage Ratings from 0V to 10V and 0V to 24V, Local Display, Cycle Time of 6ms to 90ms, (4) Relay Outputs with Voltage Ratings from 24V to 250V AC and 5V to 30V DC
- Coil Volts
- 24VDC
- Clock
- with
- Standards
- C-Tick, CSA, EN/IEC 60068-2-6 FC, EN/IEC 61000-4-11, GL, GOST, IEC 61000-4-4, UL
- Response Time
- 10 ms from state 0 to state 1)relay output || 5 ms from state 1 to state 0)relay output
- Connections - Terminals
screw terminals, 1 x 0.2 to 1 x 2.5 mm² AWG 25 to AWG 14) semi-solid || screw terminals, 1 x 0.2 to 1 x 2.5 mm² AWG 25 to AWG 14) solid || screw terminals, 1 x 0.25 to 1 x 2.5 mm² AWG 24 to AWG 14) flexible with cable end || screw terminals, 2 x 0.2 to 2 x 1.5 mm² AWG 24 to AWG 16) solid || screw terminals, 2 x 0.25 to 2 x 0.75 mm² AWG 24 to AWG 18) flexible with cable end
- Backup Time
- 10 years 25 °C
- Output Voltage Limits
- 24 to 250 V AC relay output) || 5 to 30 V DC relay output)
- Cycle Time
- 6-90 ms
- Number Or Control Scheme Lines
- 120-120 ladder || 0-200 FBD
- Kit Composition
- SR2B121BD || cable PC SR2USB01 for connection to PC
- Rated Impulse Withstand Voltage
- 4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1
- Tightening Torque
- 0.5 N.m
- Operating Rate In Hz
- 0.1 Hz at Ie)relay output || 10 Hz no load)relay output
- Relative Humidity
- 95-95 % without condensation or dripping water
- Checks
- program memory on each power up
- Immunity To Microbreaks
- 1 ms
- Electrical Durability
- AC-12 500000 cycles 230 V, 1.5 A relay output EN/IEC 60947-5-1 || AC-15 500000 cycles 230 V, 0.9 A relay output EN/IEC 60947-5-1 || DC-12 500000 cycles 24 V, 1.5 A relay output EN/IEC 60947-5-1 || DC-13 500000 cycles 24 V, 0.6 A relay output EN/IEC 60947-5-1
- Supply Voltage Limits
- 19.2-30 V
- Switching Capacity In Ma
- >= 10 mA 12 V relay output)
- Number of outputs
- 4 relay
- Ip Degree Of Protection
- IP20 IEC 60529 terminal block) || IP40 IEC 60529 front panel)
- Input Impedance
- 12 kOhm IB to IG used as analogue input circuit || 12 kOhm IB to IG used as discrete input circuit || 7.4 kOhm I1 to IA and IH to IR discrete input circuit
- Local Display
- with
- Operating Distance
- 10 m between stations, with screened cable (sensor not isolated) analogue input circuit
- Voltage State 1 Guaranteed
- >= 15 V I1 to IA and IH to IR discrete input circuit || >= 15 V IB to IG used as discrete input circuit
- Current State 1 Guaranteed
- >= 1.2 mA IB to IG used as discrete input circuit) || >= 2.2 mA I1 to IA and IH to IR discrete input circuit)
- Product Or Component Type
- compact discovery packs
- [Uimp] Rated Impulse Withstand Voltage
- 4 kVEN/IEC 60947-1 and EN/IEC 60664-1
- Input Compatibility
- 3-wire proximity sensors PNP discrete input
- Operating Altitude
- 6561.68 ft (2000 m)
- Disturbance Radiated/Conducted
- class B EN 55022-11 group 1
- Power Dissipation In W
- 3 W without extension
- Mechanical Durability
- 10000000 cycles relay output
- Discrete Input Number
- 8 EN/IEC 61131-2 type 1
- Pollution Degree
- 2 EN/IEC 61131-2
- Analogue Input Range
- 0 to 10 V || 0 to 24 V
- Analogue Input Resolution
- 8 bits
- Conversion Error
- +/- 5 % 25 °C analogue input circuit || +/- 6.2 % 55 °C analogue input circuit
- Conversion Time
- smart relay cycle time analogue input circuit
- Voltage State 0 Guaranteed
- <= 5 V I1 to IA and IH to IR discrete input circuit || <= 5 V IB to IG used as discrete input circuit
- Clock Drift
- 12 min/year 0-55 °C || 6 s/month 25-25 °C
- Ambient Air Temperature For Storage
- -40-70 °C
- Discrete Input Type
- resistive
- Analogue Input Number
- 4
- Lsb Value
- 39 mV analogue input circuit
- [Us] Rated Supply Voltage
- 24 V
- Overvoltage Category
- III EN/IEC 60664-1
- Maximum Supply Current
- 100 mA without extension)
- Repeat Accuracy
- +/- 2 % 55 °C analogue input circuit
- Product Certifications
- CSA || C-tick || UL || GOST || GL
- Counting Frequency
- 1 kHz discrete input
- Temperature Probe Type
- NTC 10k 25 °C || NTC 1000k 25 °C || KTY81 210/220/221/222/250 || Pt 500
- Ambient Air Temperature For Operation
- -20-40 °C in non-ventilated enclosure IEC 60068-2-1 and IEC 60068-2-2 || -20-55 °C IEC 60068-2-1 and IEC 60068-2-2
- Output Thermal Current
- 8 A for all 4 outputs relay output
- Current State 0 Guaranteed
- <= 0.5 mA IB to IG used as discrete input circuit) || <= 0.75 mA I1 to IA and IH to IR discrete input circuit)
- Reverse Polarity Protection
- with
- Environmental Characteristic
- EMC directive EN/IEC 61000-6-2 || EMC directive EN/IEC 61000-6-3 || EMC directive EN/IEC 61000-6-4 || EMC directive EN/IEC 61131-2 zone B || low voltage directive EN/IEC 61131-2
- Discrete Input Voltage
- 24 V DC
- Discrete Input Current
- 4 mA
- Input/Output Number
- 12
- Contacts Type And Composition
- NO relay output
- Maximum Permissible Voltage
- 30 V analogue input circuit
- Analogue Input Type
- common mode
- Maximum Altitude Transport
- 3048 m
- Product Type
- Compact Discovery Pack
- Compatible with Series
- SR2, SR3