Item
IEC Magnetic Contactor
Auxiliary Contact Form
1NC/1NO
Reversing Capability
Reversing
Terminal Connection Type
Screw Clamp
Number of Auxillary Contacts
2
Standards
BV, CCC, CSA, CSA C22.2 No 14, DNV, EN 60947-4-1, EN 60947-5-1, GL, GOST, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, LROS, RINA, UKCA, UL 508, UL Listed
Includes
Electrical Interlock, Mechanical Interlock
Enclosure NEMA Rating
No Enclosure
HP @ 3 Phase - 575V
10 hp
Frame / Series / Class / Code
TeSys
Rated Insulation Volts
600/690V
Rated Short-Time Withstand Current
30 A (at 40°C for 10 min Power Circuit), 61 A (at 40°C for 1 min Power Circuit), 105 A (at 40°C for 10 s Power Circuit), 210 A (at 40°C for 1 s Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit)
Fuse Amps
10 A (Signalling Circuit), 40 A (Type 1 Power Circuit), 25 A (Type 2 Power Circuit)
Control Circuit Voltage Limits
Drop-Out AC: 0.3 to 0.6 Uc (at -40 to 70°C 50/60 Hz); Operational AC: 0.8 to 1.1 Uc (at -40 to 60°C 50 Hz), 0.85 to 1.1 Uc (at -40 to 60°C 60 Hz), 1 to 1.1 Uc (at 60 to 70°C 50/60 Hz)
Mechanical Durability
15 Mcycles
Rated Making Capacity
250 A @ 440V (Power Circuit), 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit)
Application
Motor Control, Resistive Load
Hold VA
7.5 VA (at 60 Hz 20°C), 7 VA (at 50 Hz 20°C)
Shock Resistance
15 G for 11 ms (Contactor Closed), 10 G for 11 ms (Contactor Open)
Switching Voltage
17 V (Signalling Circuit)
Rated Breaking Capacity
250 A @ 440V
Overvoltage Category
CAT III
Operating Time
12 to 22 ms (Closing), 4 to 19 ms (Opening)
Signalling Circuit Frequency
25 to 400 Hz
Operating Speed
3600 cycles per hr
Impulse Withstand Voltage
6 kV
Tightening Torque
1.7 Nm (Control Circuit), 1.7 to 2.5 Nm (Power Circuit)
Max. Operating Watts
3 kW (at 220 to 230V AC 50 Hz), 5.5 kW (at 380 to 400V AC 50 Hz), 5.5 kW (at 415 to 440V AC 50 Hz), 7.5 kW (at 500V AC 50 Hz), 7.5 kW (at 660 to 690V AC 50 Hz)
Switching Current
5 mA (Signalling Circuit)
Features
Without Built-In Suppressor Module; Preassembled with Reversing Power Busbar
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Vibration Resistance
4 G (Contactor Closed), 2 G (Contactor Open)
Includes Protective Cover
Yes
Electrical Durability
2 Mcycles (12 A, AC-3, Less than 440 V); 0.8 Mcycles (25 A, AC-1, Less than 440 V)
Environmental Attributes
Mercury Free, PVC Free, Toxic Heavy Metal Free, Pollution Degree 3
Horsepower @ Single Phase - 120V AC
1 hp
Horsepower @ Three Phase - 600V AC
10 hp
Maximum Voltage Rating
690V AC
Horsepower @ Single Phase - 240V AC
2 hp
Resistance Properties
Fire Resistant, Insulation Resistant
Maximum Operating Temperature
140 Degrees F
Electrical Operating Durability
2,000,000, 800,000
NEMA Enclosure Rating
No Enclosure
Embedded Surge Suppressor
No
Full Load Current - Resistive
25 A
Number of Normally Open Main Contacts
3
Horsepower @ Three Phase - 240V AC
3 hp
Mounting Style
DIN Rail, Plate
Horsepower @ Three Phase - 480V AC
7 1/2 hp
Minimum Operating Temperature
-40 Degrees F
Full Load Current - Inductive
12:00 AM
Mechanical Operating Durability
15,000,000
Horsepower @ Three Phase - 208V AC
3 hp
Includes Auxiliary Contacts
Yes
Climatic Withstand
IACS E10; IEC 60947-1 Annex Q category D
Rated Operational Voltage
Power circuit Less than or Equal to 690 V AC 25 to 400 Hz; Power circuit Less than or Equal to 300 V DC
Auxiliary Contacts Type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1; Mirror contact 1 NC IEC 60947-4-1
Fire Resistance
1562°F (850°C) IEC 60695-2-1
Power Dissipation Per Pole
1.56 W AC-1; 0.36 W AC-3
Ambient Air Temperature For Operation
-40 to 140°F (-40 to 60°C); 140 to 158°F (60 to 70°C) with derating
Maximum Operating Rate
3600 cyc/h 140°F (60°C)
Conventional Free Air Thermal Current
10 A (at 140°F (60°C)) for signalling circuit; 25 A (at 140°F (60°C)) for power circuit
Device Presentation
Preassembled with reversing power busbar
Operating Altitude
0 to 9842.52 ft (0 to 3000 m)
Product Name
TeSys D; TeSys Deca
Contactor Application
Resistive load; Motor control
Control Circuit Type
AC 50/60 Hz
Rated Operational Current
25 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-1 for power circuit; 12 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-3 for power circuit
Protective Treatment
TH IEC 60068-2-30
Control Circuit Voltage
120 V AC 50/60 Hz
Utilisation Category
AC-3; AC-1
Heat Dissipation
2 to 3 W 50/60 Hz
Interlocking Type
Electrical and mechanical
Ambient Air Temperature For Storage
-76 to 176°F (-60 to 80°C)
Inrush Power in VA
70 VA 60 Hz cos phi 0.75 (at 68°F (20°C)); 70 VA 50 Hz cos phi 0.75 (at 68°F (20°C))
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical Robustness
Vibrations contactor open2 Gn, 5 to 300 Hz; Vibrations contactor closed4 Gn, 5 to 300 Hz; Shocks contactor open10 Gn for 11 ms; Shocks contactor closed15 Gn for 11 ms
Pole Contact Composition
3 NO