IEC Magnetic Contactor, 1NC/1NO, 208V AC, 3 P, Non-Reversing, Screw Clamp

  • Mfr # LC1D80L6

  • Zoro # G0896637


product price:  $496.99
/ea
Free Shipping & Returns

Key Features

Auxiliary Contact Form
1NC/1NO
Coil Voltage
208V AC
Number of Poles
3
Reversing Capability
Non-Reversing
Terminal Connection Type
Screw Clamp
See all product information
Get a 10% off coupon
Free 30-day returns
Return Policy
Get 30 days to pay with Net 30
Apply Now
Unlock tax-exempt savings
Add Tax Exemption

Specifications

Product Information

MFR #
LC1D80L6
Zoro #
G0896637
UPC #
785901207993
Country of Origin
Czechia

Dimensions

Working Height
Up to 9842.52 ft
Overall Depth
5.12 in
Overall Height
5 in
Overall Width
3.35 in

Details

Item
IEC Magnetic Contactor
Auxiliary Contact Form
1NC/1NO
Coil Voltage
208V AC
Number of Poles
3
Reversing Capability
Non-Reversing
Terminal Connection Type
Screw Clamp
Number of Auxillary Contacts
2
Standards
BV, CCC, CSA, CSA C22.2 No 14, DNV, EN 60947-4-1, EN 60947-5-1, GL, GOST, IEC 60947-4-1, IEC 60947-5-1, LROS, RINA, UL 508, UL Listed
Reversing
No
HP @ 1 Phase - 230V
15
Frame / Series / Class / Code
TeSys
Enclosure NEMA Rating
No Enclosure
HP @ 3 Phase - 575V
60 hp
Series
TeSys Deca
Shock Resistance
10 G for 11 ms (Contactor Closed), 8 G for 11 ms (Contactor Open)
Control Circuit Voltage Limits
Operational AC: 0.85 to 1.1 Uc (at -40 to 55°C 60 Hz), 1 to 1.1 Uc (at 55 to 70°C 60 Hz); Drop-Out AC: 0.3 to 0.6 Uc (at -40 to 70°C 60 Hz)
Rated Insulation Volts
600/1000V (Power Circuit), 600/690V (Signalling Circuit)
Mechanical Durability
10 Mcycles
Watts Loss
6 to 10W
Impedance
0.8 mOhm
Fire Rating
UL 94 V1
Inrush VA
220 VA
Fuse Amps
10 A (Signalling Circuit), 200 A (Type 1 Power Circuit), 160 A (Type 2 Power Circuit)
Impulse Withstand Voltage
8 kV
Rated Making Capacity
140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit), 1100 A @ 440V (Power Circuit)
Signalling Circuit Frequency
25 to 400 Hz
Features
Without Built-In Suppressor Module
Hold VA
22 VA
Net Weight
1.59 kg
IP Rating
IP20
Overvoltage Category
CAT III
Max. Operating Watts
22 kW (at 220 to 230V AC 50/60 Hz AC-3), 37 kW (at 380 to 400V AC 50/60 Hz AC-3), 45 kW (at 415 to 440V AC 50/60 Hz AC-3), 55 kW (at 500V AC 50/60 Hz AC-3), 45 kW (at 660 to 690V AC 50/60 Hz AC-3), 15 kW (at 400V AC 50/60 Hz AC-4), 22 kW (at 220 to 230V AC 50/60 Hz AC-3e), 37 kW (at 380 to 400V AC 50/60 Hz AC-3e), 45 kW (at 415 to 440V AC 50/60 Hz AC-3e), 55 kW (at 500V AC 50/60 Hz AC-3e), 45 kW (at 660 to 690V AC 50/60 Hz AC-3e)
Rated Short-Time Withstand Current
640 A (at 40°C for 10 s Power Circuit), 990 A (at 40°C for 1 s Power Circuit), 135 A (at 40°C for 10 min Power Circuit), 320 A (at 40°C for 1 min Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit)
Operating Time
20 to 35 ms (Closing), 6 to 20 ms (Opening)
Environmental Attributes
Mercury Free, PVC Free, Toxic Heavy Metal Free, Pollution Degree 3
Operating Speed
3600 cycles per hr
Switching Current
5 mA (Signalling Circuit)
Electrical Durability
0.8 Mcycles (125 A, AC-1, Less than 440 V); 1.5 Mcycles (80 A, AC-3, Less than 440 V); 1.5 Mcycles (80 A, AC-3e, Less than 440 V)
Rated Breaking Capacity
1100 A @ 440V
Includes Protective Cover
Yes
Tightening Torque
1.2 Nm (Control Circuit), 12 Nm (Power Circuit)
Switching Voltage
17 V (Signalling Circuit)
Non-Overlap Time
1.5 ms
Vibration Resistance
3 G (Contactor Closed), 2 G (Contactor Open)
Application
Motor Control, Resistive Load
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Horsepower @ Three Phase - 600V AC
60 hp
Maximum Voltage Rating
300V DC
Number of Normally Open Main Contacts
3
Maximum Operating Temperature
140 Degrees F
Contactor Style
IEC
Electrical Operating Durability
1,500,000, 800,000
Embedded Surge Suppressor
No
Phase
Three
NEMA Enclosure Rating
No Enclosure
Frequency
60 Hz
Horsepower @ Single Phase - 240V AC
15 hp
Mounting Style
DIN Rail, Plate
Minimum Operating Temperature
-40 Degrees F
Horsepower @ Three Phase - 208V AC
30 hp
Includes Auxiliary Contacts
Yes
Mechanical Operating Durability
10,000,000
Resistance Properties
Fire Resistant, Insulation Resistant
Horsepower @ Three Phase - 240V AC
30 hp
Horsepower @ Three Phase - 480V AC
60 hp
Full Load Current - Resistive
125 A
Full Load Current - Inductive
80 A
Horsepower @ Single Phase - 120V AC
7 1/2 hp
Conventional Free Air Thermal Current
10 A (at 60°C Signalling Circuit), 125 A (at 60°C Power Circuit)

Description

The IEC Magnetic Contactor (TeSys Deca) is a three‐pole, non‐reversing, electrically operated switch rated for operation within specified electrical parameters. It has 1 normally open and 1 normally closed auxiliary contact (2 total) and is designed for use with coils rated at 208 V AC. Classified as an IEC contactor, it is suitable for controlling motors and resistive loads within specified ratings and is compatible with standard control panel configurations as per manufacturer specifications.

Key features:

  • Poles and contacts: 3 main contacts (3 normally open) with 2 auxiliary contacts (1NO/1NC)
  • Coil voltage: 208 V AC
  • Reversing: non-reversing configuration (if applicable)
  • Series/format: IEC Contactor, TeSys Deca
  • Electrical characteristics: 60 Hz, Three-phase
  • Enclosure/IP: IP20; No Enclosure
  • Mechanical/electrical durability: 10 Mcycles mechanical; 1,500,000 cycles (80 A AC-3, <440 V) and 0.8 Mcycles (125 A AC-1, <440 V)
  • Power and currents: rated horsepower capacities are based on specific voltage conditions; refer to technical specifications for detailed ratings
  • Rated voltages: rated voltages are within specified operational limits according to manufacturer data
  • Rated making capacity: maximum switching capacity under specified test conditions; actual performance may vary depending on application conditions
  • Physical dimensions and weight: Depth 5.12 in; Width 3.35 in; Height 5.00 in; Net weight 1.59 kg
  • Connection and mounting: Screw Clamp terminals; Mounting on DIN Rail or Plate; Mounts on Plate, Rail
  • Additional notes: Includes protective cover; Embedded surge suppressor not present; Hold current 22 VA; Inrush 220 VA

Ratings & Reviews

3 Reasons You Can Count On Us

  • Supplies for every job.

    Supplies for every job.

    10 million items and the exact one you need.

  • When you need it fast, count on Zoro!

    When you need it fast, count on Zoro!

    2 million products ship in 1 day.

  • Stretch your budget further.

    Stretch your budget further.

    Everyday low prices on the brands you love.