- Item
- IEC Magnetic Contactor
- Auxiliary Contact Form
- No Auxiliary Contacts
- Coil Voltage
- 120V AC
- Number of Poles
- 4
- Full Load Amps-Inductive
- 9 A
- Full Load Amps-Resistive
- 20 A
- Reversing Capability
- Non-Reversing
- Terminal Connection Type
- Screw Clamp
- Number of Auxillary Contacts
- 0
- Standards
- BS 5424, CSA, IEC 60947, NF C 63-110, UKCA, UL Listed, VDE 0660
- Series
- TeSys K
- Enclosure NEMA Rating
- No Enclosure
- Reversing
- No
- Frame / Series / Class / Code
- TeSys
- Tightening Torque
- 0.8 to 1.3 Nm
- Shock Resistance
- 10 G for 11 ms (on X axis with Contactor Closed), 15 G for 11 ms (on Y and Z axis with Contactor Closed), 6 G for 11 ms (on X axis with Contactor Open), 10 G for 11 ms (on Y and Z axis with Contactor Open)
- Fire Rating
- UL 94 V1, NF F 16-101, NF F 16-102
- Impulse Withstand Voltage
- 8 kV
- Vibration Resistance
- 4 G (Contactor Closed), 2 G (Contactor Open)
- Impedance
- 3 mOhm
- Environmental Attributes
- Mercury Free, Toxic Heavy Metal Free
- IP Rating
- IP22
- Fuse Amps
- 25 A
- Rated Insulation Volts
- 600/690V
- Control Circuit Voltage Limits
- Operational: 0.8 to 1.15 Uc (at 50°C), Drop-Out: 0.2 to 0.75 Uc (at 50°C)
- Inrush VA
- 30 VA
- Rated Short-Time Withstand Current
- 90 A (at 50°C for 1 s Power Circuit), 85 A (at 50°C for 5 s Power Circuit), 80 A (at 50°C for 10 s Power Circuit), 60 A (at 50°C for 30 s Power Circuit), 45 A (at 50°C for 1 min Power Circuit), 40 A (at 50°C for 3 min Power Circuit), 20 A (at 50°C for 15 min Power Circuit)
- Rated Breaking Capacity
- 110 A @ 415V, 440V, 220 to 230V, 380 to 400 V; 80 A @ 500V; 70 A @ 660 to 690V
- Net Weight
- 0.18 kg
- Signalling Circuit Frequency
- Less Than 400 Hz
- Rated Making Capacity
- 110 A (AC Power Circuit)
- Electrical Durability
- 0.18 Mcycles (20 A, AC-1, Less than 440 V)
- Operating Time
- 10 to 20 ms (Coil De-Energisation and NO Opening), 10 to 20 ms (Coil Energisation and NO Closing), 15 to 25 ms (Coil De-Energisation and NC Closing), 5 to 15 ms (Coil Energisation and NC Opening)
- Overvoltage Category
- CAT III
- Mechanical Durability
- 10 Mcycles
- Application
- Resistive Load
- Operating Speed
- 3600 cycles per hr
- Watts Loss
- 1.3W
- Hold VA
- 4.5 VA
- Number of Normally Open Main Contacts
- 2
- Mounting Style
- DIN Rail, Plate
- Contactor Style
- IEC
- Full Load Current - Inductive
- 9 A
- Maximum Voltage Rating
- 690V AC
- Electrical Operating Durability
- 180,000
- NEMA Enclosure Rating
- No Enclosure
- Number of Normally Closed Main Contacts
- 2
- Embedded Surge Suppressor
- No
- Mechanical Operating Durability
- 10,000,000
- Full Load Current - Resistive
- 20 A
- Includes Auxiliary Contacts
- No
- Frequency
- 50/60 Hz
- Conventional Free Air Thermal Current
- 20 A (at 140°F (60°C)) for power circuit; 10 A (at 122°F (50°C)) for signalling circuit
- Heat Dissipation
- 1.3 W
- Protective Treatment
- TC IEC 60068; TC DIN 50016
- Rated Operational Voltage
- Power circuit Less than or Equal to 690 V AC Less than or Equal to 400 Hz; Signalling circuit Less than or Equal to 690 V AC Less than or Equal to 400 Hz
- Control Circuit Voltage
- 120 V AC 50/60 Hz
- Device Application
- Control
- Control Circuit Type
- AC 50/60 Hz
- Rated Operational Current
- 20 A (at Less than 140°F (60°C)) at Less than or Equal to 690 V AC AC-1 for power circuit
- Mechanical Robustness
Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27; Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27; Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27; Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27; Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27; Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27; Vibrations contactor closed4 Gn, 5 to 300 Hz IEC 60068-2-6; Vibrations contactor opened2 Gn, 5 to 300 Hz IEC 60068-2-6
- Utilisation Category
- AC-1
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Ambient Air Temperature For Storage
- -58 to 176°F (-50 to 80°C)
- Inrush Power in VA
- 30 VA (at 68°F (20°C))
- Maximum Operating Rate
- 3600 cyc/h
- Operating Altitude
- 6561.68 ft (2000 m) without derating
- Pole Contact Composition
- 2 NO + 2 NC