- Standards
- 73/23/EEC || 93/68/EEC || EN 50082-1/2 || 89/336/EEC || EN 50081-1/2 || IEC 61812-1 || IEC 60669-2-3
- Item
- Timer,250VAC,5A,Re48 +options
- Power Consumption In W
- 0.5 W 24 V || 1.7 W 240 V
- Protection Against Electric Shocks
- 4 kV class III IEC 60664-1 || 4 kV class III IEC 61812-1
- Humidity Drift
- +/- 0.05 %/%RH of the maximum setting value IEC 61812-1
- Minimum Switching Current
- 100 mA
- Breaking Capacity
- 1250 VA
- Ambient Air Temperature For Operation
- -20-50°C
- On-Load Factor
- 1
- Repeat Accuracy
- +/- 0.2 % of the maximum setting value IEC 61812-1
- Minimum Pulse Duration
- 20 ms
- Time Delay Range
- 5...300 h || 2...120 min || 0.5...30 h || 0.2...12 h || 0.2...12 min || 0.2...12 s || 0.5...30 min || 2...120 h || 2...120 s || 0.02...1.2 s || 0.5...30 s || 5...300 s || 0.05...3 s || 5...300 min
- Maximum Switching Current
- 5A
- Voltage Drift
- +/- 0.2 %/V of the maximum setting value 48...240 V || +/- 1 %/V of the maximum setting value 24...48 V
- Component Name
- RE48
- Immunity To Voltage Dips
- 30 % / 10 ms EN/IEC 61000-4-11 || 60 % / 100 ms EN/IEC 61000-4-11 || 95 % / 5 s EN/IEC 61000-4-11
- Relative Humidity
- 93-93 % without condensation IEC 60068-2-3
- Dielectric Strength
- 1 kV 1 mA/1 minute IEC 61812-1
- Ip Degree Of Protection
- IP40 IEC 60529 housing) || IP50 IEC 60529 front face)
- Voltage Range
- 0.85...1.1 Us AC || 0.9...1.1 Us DC
- Control Type
- selector switch front panel
- Marking
- CE
- Reset Time
- 25 ms on de-energisation
- Line Rated Current
- 5A
- Output Voltage
- 240 V 5 A AC-12 || 30 V 2 A DC-13 || 240 V 1.5 A AC-15
- Local Signalling
- for output relay state 1 LED (yellow) || for flashing: relay energised timing in progress LED indicator (green) || for on steady: relay energised, no timing in progress LED indicator (green)
- Mounting Support
- panel mounted: system supplied with the product || base mounted: socket
- Setting Accuracy Of Time Delay
- +/- 5 % of full scale 25°C IEC 61812-1
- Housing Material
- self-extinguishing
- Temperature Drift
- +/- 0.02 %/°C of the maximum setting value IEC 61812-1
- [Us] Rated Supply Voltage
- 24...240 V AC/DC 50/60 Hz
- Surge Withstand
- 1 kV differential mode IEC 61000-4-5 level 3 || 2 kV common mode IEC 61000-4-5 level 3
- Electrical Connection
- plug-in sub-base 8
- Mechanical Durability
- 30000000 cycles
- Discrete Output Type
- relay
- Power Consumption In Va
- 1.1 VA 24 V || 4.8 VA 240 V
- Immunity To Radioelectric Fields
- 10 V 0.15...80 MHz)EN/IEC 61000-4-6 level 3
- Contacts Type And Composition
- 2 C/O timed contacts, AgNi (cadmium free)
- Product Or Component Type
- single function relay
- Time Delay Type
- power on-delay
- Resistance To Electromagnetic Fields
- 10 V/m 26 MHz to 1 GHz IEC 61000-4-3 level 3
- Electrical Durability
- 100000 cycles
- Immunity To Microbreaks
- 10 ms
- Product Certifications
- UL || cULus || C-tick || CSA
- Disturbance Radiated/Conducted
- class B 0.15...30 MHz EN 55022 (EN 55011 group 1)
- Resistance To Fast Transients
- 2 kV EN/IEC 61000-4-4 level 4 capacitive connecting clip) || 4 kV EN/IEC 61000-4-4 level 4 direct)
- Resistance To Electrostatic Discharge
- 6 kV in contact EN/IEC 61000-4-2 level 3 || 8 kV in air EN/IEC 61000-4-2 level 3
- Vibration Resistance
- 0.35 mm 10-55 Hz)IEC 60068-2-6
- Ambient Air Temperature For Storage
- -40-70°C
- Pick Up Duration
- 55 ms
- Maximum Switching Voltage
- 250 V AC/DC
- Range of Product
- Harmony Timer Relays