Minimum Required Rack Depth with External Battery Pack (in.)
30.25
UPS Input Cord Length (ft.)
10
Minimum Required Rack Depth without External Battery Pack (in.)
29.25
Details
Item
Smart UPS
UPS Type
Online
Power Rating
3000VA
Mounting
Rack
Wattage
2700 W
Input Voltage
208V AC
Output Voltage
120/208V
Backup Time (Half/Full Load)
13.5 min/5 min
Number of Outlets
20
Transfer Time
No transfer time (0 ms.) in online, double-conversion mode; 4 ms. transfer time during economy mode operation
Hz
60 Hz
NEMA Plug Configuration
L5-30P
NEMA Receptacle Configuration
(12) 5-15/20R; (6) 6-15/20R; (2) L6-20R
Housing Material
Metal
UPS Certifications
Meets FCC Part 15 Category A (EMI); Tested to CSA (Canada); Tested to NOM (Mexico); Tested to UL1778 (USA)
Output Watt Capacity (Watts)
2700
Switches
5 front panel switches: On/Off, Up, Down and Escape
High Voltage Transfer to Battery Power (Setpoint)
288V
Relative Humidity
5 to 95%, non-condensing
Included Mounting Accessory Description
4 post installation accessories included (2 sets)
Battery Mode BTU / Hr. (Full Load)
1399
Output kVA Capacity (kVA)
3
Network Monitoring Port Description
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 plus assignable contact closure pin functions for On-battery, On bypass, Output-on and Low-battery conditions and remote Shutdown, Output-off, Reboot and Power-toggle operations
Battery Replacement Description
Hot-swappable, replaceable batteries
Front Panel LCD Display
Interactive front-panel LCD interface reports UPS operating mode, detailed UPS status and site-power information; LCD interface also enables a variety of advanced UPS setup and configuration options
Output Volt Amp Capacity (VA)
3000
Audible Alarm
Audible alarm indicates power failure, low battery, overload and fault
Expandable Battery Runtime
Supports extended runtime with optional external battery packs
Communications Cable
USB and DB9 cabling included
Primary Form Factor
Rackmount
Individually Controllable Load Banks
Yes
Undervoltage Correction
2% output voltage regulation during undervoltages to 160V (100% load), 130V (70% load), 100V (30% load)
Automatic inverter bypass; Battery Independent Restart; Hot swappable batteries
LED Indicators
4 front panel LEDs: AC input (green), AC output (green), Battery (yellow), Fault (red)
Network Management Cards
SNMPWEBCARD ; WEBCARDLX
Installation Form Factors Supported with Optional Accessories
2 post rackmount ( 2POSTRMKITWM ); Tower ( 2-9USTAND )
Full Load Runtime (min.)
5 min. (2700w)
Voltage Regulation Description
Online, double-conversion power conditioning
AC Suppression Joule Rating
570
AC Suppression Response Time
Instantaneous
PowerAlert Software
For local monitoring via the UPS™s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
DC System Voltage (VDC)
72
Output Circuit Breakers
Included 2U transformer module includes four 20A 120V circuit breakers (each protects 3 NEMA 5-15/20R outlets).
Output Voltage Regulation (Economy Line Mode)
+/- 10%
Rated input current (Maximum Load)
14.97A
Battery Access
Front panel battery access door
Nominal Output Voltage(s) Supported
120V; 208V
Crest Factor
0.125694444444444
Installation Form Factors Supported with Included Accessories
4 post 19 inch rackmount
Grounding Lug
Back panel grounding lug included
Overvoltage Correction
2% output voltage regulation during overvoltages to 288
Load Management Receptacles
Two switchable outlet load banks (2 NEMA 6-15/20R outlets per bank)
Internal UPS Replacement Battery Cartridge
RBC72S
Battery Recharge Rate (Included Batteries)
3.0 hours from 10% to 90% (typical, full load discharge)
Half Load Runtime (min.)
13.5 min. (1350w)
UPS Dataline Suppression Details
Single line dialup / network dataline protection included
Nominal Input Voltage(s) Supported
208V AC
Frequency Compatibility Details
IMPORTANT! Please ensure the UPS is configured for 60Hz output when used with the included step-down transformer module
Output Voltage Regulation (Line Mode)
+/- 2%
Output kW Capacity (kW)
2.7
Power Factor
0.9
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.
Input Phase
Single-Phase
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.
Output Capacity Details
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% for 3 minutes, 150% for 30 seconds and >150% for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits).
Output AC Waveform (Battery Mode)
Pure Sine wave
Output Voltage Regulation (Battery Mode)
+/- 2%
AC Economy Mode BTU / Hr. (Full Load)
588
Alarm Cancel Operation
Power-fail alarm can be silenced by following on-screen prompts