Item
IEC Magnetic Contactor
Auxiliary Contact Form
1NC/1NO
Reversing Capability
Reversing
Terminal Connection Type
Screw Clamp
Number of Auxillary Contacts
2
Standards
BV, CCC, CSA, CSA C22.2 No 14, DNV, EN 60947-4-1, EN 60947-5-1, GL, GOST, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, LROS, RINA, UKCA, UL 508, UL Listed
Frame / Series / Class / Code
TeSys
Enclosure NEMA Rating
No Enclosure
HP @ 3 Phase - 575V
20 hp
Switching Voltage
17 V (Signalling Circuit)
Includes Protective Cover
Yes
Max. Operating Watts
5.5 kW (at 220 to 230V AC 50 Hz), 11 kW (at 380 to 400V AC 50 Hz), 11 kW (at 415 to 440V AC 50 Hz), 15 kW (at 500V AC 50 Hz), 15 kW (at 660 to 690V AC 50 Hz)
Impulse Withstand Voltage
6 kV
Shock Resistance
8 G for 11 ms (Contactor Open), 15 G for 11 ms (Contactor Closed)
Application
Motor Control, Resistive Load
Rated Making Capacity
140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit), 450 A @ 440V (Power Circuit)
Rated Breaking Capacity
450 A @ 440V
Mechanical Durability
15 Mcycles
Electrical Durability
1.65 Mcycles (25 A, AC-3, Less than 440 V); 1.4 Mcycles (40 A, AC-1, Less than 440 V)
Vibration Resistance
4 G (Contactor Closed), 2 G (Contactor Open)
Tightening Torque
1.7 Nm (Control Circuit), 2.5 Nm (Power Circuit)
Environmental Attributes
Mercury Free, PVC Free, Toxic Heavy Metal Free, Pollution Degree 3
Fuse Amps
10 A (Signalling Circuit), 63 A (Type 1 Power Circuit), 40 A (Type 2 Power Circuit)
Overvoltage Category
CAT III
Switching Current
5 mA (Signalling Circuit)
Operating Speed
3600 cycles per hr
Features
Without Built-In Suppressor Module; Preassembled with Reversing Power Busbar
Control Circuit Voltage Limits
Drop-Out AC: 0.3 to 0.6 Uc (at -40 to 70°C 50/60 Hz); Operational AC: 0.8 to 1.1 Uc (at -40 to 60°C 50 Hz), 0.85 to 1.1 Uc (at -40 to 60°C 60 Hz), 1 to 1.1 Uc (at 60 to 70°C 50/60 Hz)
Signalling Circuit Frequency
25 to 400 Hz
Rated Insulation Volts
600/690V
Hold VA
7.5 VA (at 60 Hz 20°C), 7 VA (at 50 Hz 20°C)
Operating Time
12 to 22 ms (Closing), 4 to 19 ms (Opening)
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Rated Short-Time Withstand Current
50 A (at 40°C for 10 min Power Circuit), 120 A (at 40°C for 1 min Power Circuit), 240 A (at 40°C for 10 s Power Circuit), 380 A (at 40°C for 1 s Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit)
Minimum Operating Temperature
-40 Degrees F
Mechanical Operating Durability
15,000,000
Horsepower @ Single Phase - 240V AC
3 hp
Mounting Style
DIN Rail, Plate
Electrical Operating Durability
1,400,000, 1,650,000
Maximum Operating Temperature
140 Degrees F
Horsepower @ Three Phase - 240V AC
7 1/2 hp
Horsepower @ Single Phase - 120V AC
2 hp
Full Load Current - Resistive
40 A
Maximum Voltage Rating
690V AC
Embedded Surge Suppressor
No
Includes Auxiliary Contacts
Yes
Horsepower @ Three Phase - 208V AC
5 hp
Resistance Properties
Fire Resistant, Insulation Resistant
Number of Normally Open Main Contacts
3
Full Load Current - Inductive
25 A
Horsepower @ Three Phase - 480V AC
15 hp
NEMA Enclosure Rating
No Enclosure
Horsepower @ Three Phase - 600V AC
20 hp
Climatic Withstand
IACS E10; IEC 60947-1 Annex Q category D
Mechanical Robustness
Vibrations contactor open2 Gn, 5 to 300 Hz; Vibrations contactor closed4 Gn, 5 to 300 Hz; Shocks contactor closed15 Gn for 11 ms; Shocks contactor open8 Gn for 11 ms
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Heat Dissipation
2 to 3 W 50/60 Hz
Control Circuit Voltage
120 V AC 50/60 Hz
Power Dissipation Per Pole
1.25 W AC-3; 3.2 W AC-1; 1.25 W AC-3e
Contactor Application
Motor control; Resistive load
Ambient Air Temperature For Storage
-76 to 176°F (-60 to 80°C)
Product Name
TeSys Deca; TeSys Deca
Protective Treatment
TH IEC 60068-2-30
Device Presentation
Preassembled with reversing power busbar
Rated Operational Voltage
Power circuit Less than or Equal to 690 V AC 25 to 400 Hz; Power circuit Less than or Equal to 300 V DC
Fire Resistance
1562°F (850°C) IEC 60695-2-1
Interlocking Type
Mechanical
Conventional Free Air Thermal Current
10 A (at 140°F (60°C)) for signalling circuit; 40 A (at 140°F (60°C)) for power circuit
Auxiliary Contacts Type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1; Mirror contact 1 NC IEC 60947-4-1
Utilisation Category
AC-1; AC-3; AC-3e
Control Circuit Type
AC 50/60 Hz
Operating Altitude
0 to 9842.52 ft (0 to 3000 m)
Ambient Air Temperature For Operation
-40 to 140°F (-40 to 60°C); 140 to 158°F (60 to 70°C) with derating
Maximum Operating Rate
3600 cyc/h 140°F (60°C)
Inrush Power in VA
70 VA 60 Hz cos phi 0.75 (at 68°F (20°C)); 70 VA 50 Hz cos phi 0.75 (at 68°F (20°C))
Rated Operational Current
25 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-3 for power circuit; 40 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-1 for power circuit
Pole Contact Composition
3 NO