Shop SCHNEIDER ELECTRIC

IEC Magnetic Contactor, 1NC/1NO, 208V AC, 3 P, Non-Reversing, Screw Clamp

  • Mfr # LC1D12LE7
  • Zoro # G0329847

product price: 
$
147.99
/ea
Free Shipping & Returns

Key Features

Auxiliary Contact Form
1NC/1NO
Coil Voltage
208V AC
Number of Poles
3
Full Load Amps-Inductive
12 A
Full Load Amps-Resistive
25 A
See all product information
Unlock 30-day payment terms
Unlock 30-day payment terms
Business customers can apply for Net 30—no fees, no interest, fast approval. Terms apply.
Create Account
Get 10% off your order
Get 10% off your order
Sign up for our email list and receive your promo code via email.

Specifications

Details

MFR #
LC1D12LE7
Zoro #
G0329847
UPC #
785901213208
Country of Origin
Indonesia
Item
IEC Magnetic Contactor
Auxiliary Contact Form
1NC/1NO
Coil Voltage
208V AC
Number of Poles
3
Full Load Amps-Inductive
12 A
Full Load Amps-Resistive
25 A
Reversing Capability
Non-Reversing
Terminal Connection Type
Screw Clamp
Number of Auxillary Contacts
2
Standards
BV, CCC, CSA, CSA C22.2 No 14, DNV, EN 60947-4-1, EN 60947-5-1, GL, GOST, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, LROS, RINA, UKCA, UL 508, UL Listed
HP @ 1 Phase - 230V
2
Reversing
No
Frame / Series / Class / Code
TeSys
Enclosure NEMA Rating
No Enclosure
HP @ 3 Phase - 575V
10 hp
Series
TeSys Deca
Switching Current
5 mA (Signalling Circuit)
Environmental Attributes
Mercury Free, PVC Free, Toxic Heavy Metal Free, Pollution Degree 3
Operating Time
12 to 22 ms (Closing), 4 to 19 ms (Opening)
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Electrical Durability
2 Mcycles (12 A, AC-3, Less than 440 V); 0.8 Mcycles (25 A, AC-1, Less than 440 V); 2 Mcycles (12 A, AC-3e, Less than 440 V)
Non-Overlap Time
1.5 ms
Fuse Amps
10 A (Signalling Circuit), 40 A (Type 1 Power Circuit), 25 A (Type 2 Power Circuit)
Signalling Circuit Frequency
25 to 400 Hz
Rated Breaking Capacity
250 A @ 440V
Switching Voltage
17 V (Signalling Circuit)
Operating Speed
3600 cycles per hr
Hold VA
7.5 VA (at 60 Hz 20°C), 7 VA (at 50 Hz 20°C)
Overvoltage Category
CAT III
Watts Loss
2 to 3W
Net Weight
0.325 kg
Rated Short-Time Withstand Current
105 A (at 40 Degrees C for 10 s Power Circuit), 210 A (at 40 Degrees C for 1 s Power Circuit), 30 A (at 40 Degrees C for 10 min Power Circuit), 61 A (at 40 Degrees C for 1 min Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit)
Application
Motor Control, Resistive Load
Mechanical Durability
15 Mcycles
Control Circuit Voltage Limits
Drop-Out AC: 0.3 to 0.6 Uc (at -40 to 70°C 50/60 Hz); Operational AC: 0.8 to 1.1 Uc (at -40 to 60°C 50 Hz), 0.85 to 1.1 Uc (at -40 to 60°C 60 Hz), 1 to 1.1 Uc (at 60 to 70°C 50/60 Hz)
IP Rating
IP20
Impulse Withstand Voltage
6 kV
Fire Rating
UL 94 V1
Includes Protective Cover
Yes
Rated Insulation Volts
600V, 690V
Features
Without Built-In Suppressor Module
Vibration Resistance
4 G (Contactor Closed), 2 G (Contactor Open)
Shock Resistance
15 G for 11 ms (Contactor Closed), 10 G for 11 ms (Contactor Open)
Rated Making Capacity
250 A @ 440V (Power Circuit), 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit)
Inrush VA
70 VA
Tightening Torque
1.7 Nm
Max. Operating Watts
3 kW (at 220 to 230V AC 50/60 Hz AC-3), 5.5 kW (at 380 to 400V AC 50/60 Hz AC-3), 5.5 kW 415 to (at 440V AC 50/60 Hz AC-3), 7.5 kW (at 500V AC 50/60 Hz AC-3), 7.5 kW (at 660 to 690V AC 50/60 Hz AC-3), 3.7 kW (at 400V AC 50/60 Hz AC-4), 3 kW (at 220 to 230V AC 50/60 Hz AC-3e), 5.5 kW (at 380 to 400V AC 50/60 Hz AC-3e), 5.5 kW 415 to (at 440V AC 50/60 Hz AC-3e), 7.5 kW (at 500V AC 50/60 Hz AC-3e), 7.5 kW (at 660 to 690V AC 50/60 Hz AC-3e)
Impedance
2.5 mOhm
Electrical Operating Durability
2,000,000, 800,000
Includes Auxiliary Contacts
Yes
Frequency
50/60 Hz
Minimum Operating Temperature
-40 Degrees F
Mounting Style
DIN Rail, Plate
Contactor Style
IEC
Resistance Properties
Fire Resistant, Insulation Resistant
Full Load Current - Resistive
25 A
Horsepower @ Three Phase - 480V AC
7 1/2 hp
Horsepower @ Single Phase - 120V AC
1/2 hp
Number of Normally Open Main Contacts
3
Embedded Surge Suppressor
No
Horsepower @ Single Phase - 240V AC
2 hp
Maximum Voltage Rating
690V AC
Horsepower @ Three Phase - 208V AC
3 hp
Phase
Three
Horsepower @ Three Phase - 240V AC
3 hp
Full Load Current - Inductive
12 A
Maximum Operating Temperature
140 Degrees F
Horsepower @ Three Phase - 600V AC
10 hp
NEMA Enclosure Rating
No Enclosure
Mechanical Operating Durability
15,000,000
Conventional Free Air Thermal Current
25 A (at 60°C Power Circuit), 10 A (at 60°C Signalling Circuit)

Dimensions

Working Height
Up to 9842.52 ft
Overall Height
3.03 in
Overall Depth
3.39 in
Overall Width
1.77 in

Description

The item is an IEC Magnetic Contactor (3-pole, non-reversing) from the TeSys Deca series.

  • It uses a 208 V AC coil to switch power circuits and includes auxiliary contacts as specified; actual performance may vary based on application.
  • Rated for operation with motor control and resistive loads within specified parameters; uses screw clamp terminals; no built-in surge suppressor or enclosure.
  • It is rated for operation within the specified voltage and frequency ranges and can be mounted on DIN rails or plates.
  • Action: Non-Reversing
  • Phase/Poles: Three-phase, 3 poles
  • Coil Voltage: 208 V AC
  • Auxiliary contacts: includes auxiliary contacts as specified; actual performance may vary based on application
  • Electrical ratings: Maximum voltage 690 V AC; Rated making capacity 250 A @ 440 V (Power Circuit); 140 A (AC Signalling); 250 A (DC Signalling)
  • Full Load Amps: 12 A inductive; 25 A resistive
  • Durability: durability ratings are based on testing conditions; actual lifespan may vary depending on usage
  • IP/Enclosure: IP20; No Enclosure
  • Mounting/Terminals: DIN Rail, Plate mounting; Screw Clamp terminals
  • Dimensions/Weight: Depth 3.38 in; Height 3.03 in; Width 1.77 in; Net Weight 0.325 kg
  • Series: TeSys Deca
  • Operating times: typical switching times under test conditions; actual response time may vary
  • Impulse withstand: impulse withstand voltage as tested under specific standards; does not imply immunity from all transient events
  • Includes: Auxiliary Contacts Yes; Protective Cover Yes
  • Shock resistance: 15 G (Closed); 10 G (Open)
  • Standards: BV, CCC, CSA, CSA C22.2 No 14, DNV, EN 60947-4-1, EN 60947-5-1, GL, GOST, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, LROS, RINA, UKCA, UL 508, UL Listed
  • Frequency: 50/60 Hz
  • Maximum Operating Temperature: 140 Degrees F
  • Ratings & reviews

    3 reasons you can count on us

    • Supplies for every job.

      13 million items and the exact one you need.

    • When you need it fast, count on Zoro!

      4.5 million products ship in 1 day.

    • Stretch your budget further.

      Everyday low prices on the brands you love.