Item
IEC Magnetic Contactor
Auxiliary Contact Form
1NC/1NO
Full Load Amps-Inductive
12 A
Full Load Amps-Resistive
25 A
Reversing Capability
Reversing
Terminal Connection Type
Screw Clamp
Number of Auxillary Contacts
2
Standards
CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
HP @ 3 Phase - 575V
10 hp
Fuse Amps
10 A (Signalling Circuit), 40 A (Type 1 Power Circuit), 25 A (Type 2 Power Circuit)
Switching Current
5 mA (Signalling Circuit)
Environmental Attributes
Mercury Free, PVC Free, Toxic Heavy Metal Free, Pollution Degree 3
Max. Operating Watts
3 kW (at 220 to 230V AC 50 Hz), 5.5 kW (at 380 to 400V AC 50 Hz), 5.5 kW (at 415 to 440V AC 50 Hz), 7.5 kW (at 500V AC 50 Hz), 7.5 kW (at 660 to 690V AC 50 Hz)
Shock Resistance
15 G for 11 ms (Contactor Closed), 10 G for 11 ms (Contactor Open)
Rated Making Capacity
250 A @ 440V (Power Circuit), 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit)
Vibration Resistance
4 G (Contactor Closed), 2 G (Contactor Open)
Switching Voltage
17 V (Signalling Circuit)
Control Circuit Voltage Limits
Drop-Out AC: 0.3 to 0.6 Uc (at -40 to 70°C 50/60 Hz); Operational AC: 0.8 to 1.1 Uc (at -40 to 60°C 50 Hz), 0.85 to 1.1 Uc (at -40 to 60°C 60 Hz), 1 to 1.1 Uc (at 60 to 70°C 50/60 Hz)
Rated Breaking Capacity
250 A @ 440V
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Hold VA
7.5 VA (at 60 Hz 20°C), 7 VA (at 50 Hz 20°C)
Signalling Circuit Frequency
25 to 400 Hz
Features
Without Built-In Suppressor Module; Preassembled with Reversing Power Busbar
Mechanical Durability
15 Mcycles
Application
Motor Control, Resistive Load
Rated Insulation Volts
600/690V
Includes Protective Cover
Yes
Overvoltage Category
CAT III
Electrical Durability
2 Mcycles (12 A, AC-3, Less than 440 V); 0.8 Mcycles (25 A, AC-1, Less than 440 V)
Rated Short-Time Withstand Current
30 A (at 40°C for 10 min Power Circuit), 61 A (at 40°C for 1 min Power Circuit), 105 A (at 40°C for 10 s Power Circuit), 210 A (at 40°C for 1 s Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit)
Impulse Withstand Voltage
6 kV
Operating Speed
3600 cycles per hr
Operating Time
12 to 22 ms (Closing), 4 to 19 ms (Opening)
Tightening Torque
1.7 Nm (Control Circuit), 1.7 to 2.5 Nm (Power Circuit)
Horsepower @ Three Phase - 240V AC
3 hp
Horsepower @ Single Phase - 240V AC
2 hp
Full Load Current - Resistive
25 A
Full Load Current - Inductive
12:00 AM
Horsepower @ Three Phase - 480V AC
7 1/2 hp
Horsepower @ Three Phase - 208V AC
3 hp
Horsepower @ Three Phase - 600V AC
10 hp
Electrical Operating Durability
2,000,000
Maximum Operating Temperature
60 Degrees F
Includes Auxiliary Contacts
Yes
Maximum Voltage Rating
690V AC
Mechanical Operating Durability
15,000,000
Minimum Operating Temperature
-40 Degrees F
Mounting Style
Plate, DIN Rail
Response Time
12 to 22 msec (Closing), 4 to 19 msec (Opening)
Number of Normally Open Main Contacts
3
Resistance Properties
Fire Resistant, Insulation Resistant
Conventional Free Air Thermal Current