- MFR #
- LR2K0303
- Zoro #
- G3154426
- UPC #
- 785901882732
- Country of Origin
- Korea, Republic of
- Item
- Overload Relay
- Auxiliary Contact Form
- 1NC/1NO
- Minimum Overload Relay Current Setting
- 0.23 A
- Maximum Overload Relay Current Setting
- 0.36 A
- Trip Class
- 10A
- Overload Protection Type
- Thermal
- Maximum Voltage Rating
- 690V AC
- Standards
- BS 4941, IEC 60947, NF C 63-650, REACH, RoHS, VDE 0660
- Sensing Method
- Bimetallic
- For Use With
- TeSys K AC or DC IEC Contactor
- Trip Class - Overload
- 10
- Features
- Single Phase Sensitivity; Differential
- Number of Poles
- 3
- Use With - Contactors and Starters
- LC7K, LP1K, LP4K Contactors, Mfr. Series LC1K
- Starter Type
- IEC
- Connections - Terminals
screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 2 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 0.34-1.5 mm²flexible with cable end
- Control Type
- Red push-button trip test function || Blue push-button stop and manual reset || selector switch manual or automatic reset
- Power Dissipation Per Pole
- 2 W
- Network Type
- AC || DC
- Thermal Overload Class
- class 10A IEC 60947-4-1
- Local Signalling
- trip indicator Yellow)
- Operating Altitude
- 6561.68 ft (2000 m) without derating
- Thermal Protection Adjustment Range
- 0.23-0.36 A
- Product Or Component Type
- differential thermal overload relay
- Product Name
- TeSys LRK
- Product Compatibility
- LC7K || LC1K || LP1K || LP4K
- Ambient Air Temperature For Operation
- -20-55°C without derating IEC 60947 || -30-60°C with derating IEC 60947
- Associated Fuse Rating
- 6 A gG signalling circuit VDE 0660 || 6 A gG signalling circuit IEC 60947
- Phase Failure Sensitivity
- yes IEC 60947-4-1
- Network Frequency
- <= 400 Hz
- Device Short Name
- LR2K
- Flame Retardance
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- Range
- TeSys
- Ambient Air Temperature For Storage
- -40-70°C
- Tightening Torque
- 1.3 N.m screw clamp terminals Philips No 2 || 1.3 N.m screw clamp terminals flat Ø 6 mm || 1.3 N.m screw clamp terminals pozidriv No 2
- Relay Application
- motor protection
- Protective Treatment
- TC IEC 60068 || TC DIN 50016
- Mechanical Robustness
- shocks NO contact10 Gn for 11 ms IEC 60068-2-27 || shocks NC contact10 Gn for 11 ms IEC 60068-2-27 || vibrations NO contact2 Gn, 5 to 300 Hz IEC 60068-2-6 || vibrations NC contact2 Gn, 5 to 300 Hz IEC 60068-2-6
- Fire Resistance
- 850°C IEC 60695-2-1
- Product Certifications
- UL || CSA || UKCA
- Maximum Operating Temperature
- 131 Degrees F
- Mounting Style
- Direct To Contactor
- Minimum Operating Temperature
- -4 Degrees F
- Relay Style
- IEC
- Terminal Connection Type
- Screw Clamp Terminals
- Reset Type
- Auto, Manual
- IP Rating
- IP22
- Compatible with Series
- TeSys Deca, TeSys K
- Conventional Free Air Thermal Current
- 6 A signalling circuit
- Rated Insulation Voltage
- power circuit 690 V BS 4941 || power circuit 690 V IEC 60947 || power circuit 750 V VDE 0110 group C || power circuit 600 V CSA C22.2 No 14
- Rated Operational Voltage
- <= 690 V power circuit || 690 V AC AC-15 signalling circuit || 250 V DC DC-13 signalling circuit
- Trip Clss
- 10A