Item
IEC Magnetic Contactor
Auxiliary Contact Form
1NC/1NO
Reversing Capability
Non-Reversing
Terminal Connection Type
Screw Clamp
Number of Auxillary Contacts
2
Standards
BV, CCC, CSA, CSA C22.2 No 14, DNV, EN 60947-4-1, EN 60947-5-1, GL, GOST, IEC 60947-4-1, IEC 60947-5-1, LROS, RINA, UL 508, UL Listed
HP @ 3 Phase - 575V
60 hp
Enclosure NEMA Rating
No Enclosure
Rated Breaking Capacity
1100 A @ 440V
Rated Short-Time Withstand Current
640 A (at 40°C for 10 s Power Circuit), 990 A (at 40°C for 1 s Power Circuit), 135 A (at 40°C for 10 min Power Circuit), 320 A (at 40°C for 1 min Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit)
Operating Speed
3600 cycles per hr
Impulse Withstand Voltage
8 kV
Rated Insulation Volts
600/1000V (Power Circuit), 600/690V (Signalling Circuit)
Shock Resistance
10 G for 11 ms (Contactor Closed), 8 G for 11 ms (Contactor Open)
Includes Protective Cover
Yes
Rated Making Capacity
140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit), 1100 A @ 440V (Power Circuit)
Tightening Torque
1.2 Nm (Control Circuit), 12 Nm (Power Circuit)
Overvoltage Category
CAT III
Mechanical Durability
4 Mcycles
Application
Motor Control, Resistive Load
Vibration Resistance
3 G (Contactor Closed), 2 G (Contactor Open)
Switching Voltage
17 V (Signalling Circuit)
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Switching Current
5 mA (Signalling Circuit)
Control Circuit Voltage Limits
Drop-Out DC: 0.1 to 0.3 Uc (at -40 to 70°C); Operational DC: 0.85 to 1.1 Uc (at -40 to 55°C), 1 to 1.1 Uc (at 55 to 70°C)
Environmental Attributes
Mercury Free, PVC Free, Toxic Heavy Metal Free, Pollution Degree 3
Max. Operating Watts
22 kW (at 220 to 230V AC 50 Hz AC-3), 37 kW (at 380 to 400V AC 50 Hz AC-3), 45 kW (at 415 to 440V AC 50 Hz AC-3), 55 kW (at 500V AC 50 Hz AC-3), 45 kW (at 660 to 690V AC 50 Hz AC-3), 15 kW (at 400V AC 50 Hz AC-4), 22 kW (at 220 to 230V AC 50 Hz AC-3e), 37 kW (at 380 to 400V AC 50 Hz AC-3e), 45 kW (at 415 to 440V AC 50 Hz AC-3e), 55 kW (at 500V AC 50 Hz AC-3e), 45 kW (at 660 to 690V AC 50 Hz AC-3e)
Signalling Circuit Frequency
25 to 400 Hz
Features
Without Built-In Suppressor Module
Fuse Amps
10 A (Signalling Circuit), 200 A (Type 1 Power Circuit), 160 A (Type 2 Power Circuit)
Operating Time
95 to 130 ms (Closing), 20 to 35 ms (Opening)
Electrical Durability
0.8 Mcycles (125 A, AC-1, Less than 440 V); 1.5 Mcycles (80 A, AC-3, Less than 440 V); 1.5 Mcycles (80 A, AC-3e, Less than 440 V)
Full Load Current - Inductive
80 A
Maximum Voltage Rating
300V DC
Full Load Current - Resistive
125 A
Resistance Properties
Fire Resistant, Insulation Resistant
Horsepower @ Three Phase - 208V AC
30 hp
Minimum Operating Temperature
-40 Degrees F
Maximum Operating Temperature
140 Degrees F
Horsepower @ Three Phase - 600V AC
60 hp
NEMA Enclosure Rating
No Enclosure
Number of Normally Open Main Contacts
3
Mounting Style
DIN Rail, Plate
Horsepower @ Single Phase - 240V AC
15 hp
Includes Auxiliary Contacts
Yes
Embedded Surge Suppressor
No
Horsepower @ Three Phase - 240V AC
30 hp
Horsepower @ Single Phase - 120V AC
7 1/2 hp
Horsepower @ Three Phase - 480V AC
60 hp
Mechanical Operating Durability
4,000,000
Electrical Operating Durability
1,500,000, 800,000
Conventional Free Air Thermal Current
10 A (at 60°C Signalling Circuit), 125 A (at 60°C Power Circuit)