Item
IEC Miniature Magnetic Contactor
Auxiliary Contact Form
1NO
Reversing Capability
Non-Reversing
Terminal Connection Type
Screw Clamp
Number of Auxillary Contacts
1
Standards
BS 5424, CSA, IEC 60947, NF C 63-110, UKCA, UL Listed, VDE 0660
HP @ 1 Phase - 230V
1-1/2
Frame / Series / Class / Code
TeSys
HP @ 3 Phase - 575V
10 hp
Enclosure NEMA Rating
No Enclosure
Application
Motor Control, Resistive Load
Environmental Attributes
Mercury Free, Toxic Heavy Metal Free
Mechanical Durability
10 Mcycles
Overvoltage Category
CAT III
Tightening Torque
0.8 to 1.3 Nm
Rated Making Capacity
110 A (AC Signalling Circuit), 144 A (AC Power Circuit)
Electrical Durability
0.3 Mcycles (20 A, AC-1, Less than 440 V); 1.3 Mcycles (12 A, AC-3, Less than 440 V); 1.3 Mcycles (12 A, AC-3e, Less than 440 V)
Switching Voltage
17 V (Signalling Circuit)
Vibration Resistance
4 G (Contactor Closed), 2 G (Contactor Open)
Control Circuit Voltage Limits
Operational: 0.8 to 1.15 Uc (at 50°C), Drop-Out: 0.2 to 0.75 Uc (at 50°C)
Shock Resistance
10 G for 11 ms (on X axis with Contactor Closed), 15 G for 11 ms (on Y and Z axis with Contactor Closed), 6 G for 11 ms (on X axis with Contactor Open), 10 G for 11 ms (on Y and Z axis with Contactor Open)
Rated Short-Time Withstand Current
115 A (at 50°C for 1 s Power Circuit), 105 A (at 50°C for 5 s Power Circuit), 100 A (at 50°C for 10 s Power Circuit), 75 A (at 50°C for 30 s Power Circuit), 55 A (at 50°C for 1 min Power Circuit), 50 A (at 50°C for 3 min Power Circuit), 80 A (For 1 s Signalling Circuit), 90 A (For 500 ms Signalling Circuit), 110 A (For 100 ms Signalling Circuit), 25 A (at 50°C for 15 min Power Circuit)
Fire Rating
UL 94 V1, NF F 16-101, NF F 16-102
Fuse Amps
25 A (Power Circuit), 10 A (Signalling Circuit)
Max. Operating Watts
4 kW (at 480V AC 50/60 Hz AC-3), 4 kW (at 500 to 600V AC 50/60 Hz AC-3), 4 kW (at 660 to 690V AC 50/60 Hz AC-3), 2.2 kW (at 400V AC 50/60 Hz AC-4), 3 kW (at 220 to 230V AC 50/60 Hz AC-3), 5.5 kW 380 to (at 415V AC 50/60 Hz AC-3), 5.5 kW (at 440V AC 50/60 Hz AC-3), 4 kW (at 480V AC 50/60 Hz AC-3e), 4 kW (at 500 to 600V AC 50/60 Hz AC-3e), 4 kW (at 660 to 690V AC 50/60 Hz AC-3e), 3 kW (at 220 to 230V AC 50/60 Hz AC-3e), 5.5 kW (at 380 to 415V AC 50/60 Hz AC-3e), 5.5 kW (at 440V AC 50/60 Hz AC-3e)
Signalling Circuit Frequency
Less Than 400 Hz
Rated Insulation Volts
600/690V
Rated Breaking Capacity
110 A @ 440V, 80 A @ 500V, 70 A @ 660 to 690V
Operating Speed
3600 cycles per hr
Impulse Withstand Voltage
8 kV
Operating Time
10 to 20 ms (Coil De-Energisation and NO Opening), 10 to 20 ms (Coil Energisation and NO Closing)
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Switching Current
5 mA (Signalling Circuit)
NEMA Enclosure Rating
No Enclosure
Resistance Properties
Insulation Resistant
Maximum Voltage Rating
690V AC
Mounting Style
DIN Rail, Plate
Horsepower @ Three Phase - 480V AC
7 1/2 hp
Full Load Current - Resistive
20 A
Full Load Current - Inductive
12:00 AM
Horsepower @ Three Phase - 240V AC
3 hp
Electrical Operating Durability
1,300,000, 300,000
Number of Normally Open Main Contacts
3
Horsepower @ Single Phase - 240V AC
2 hp
Horsepower @ Single Phase - 120V AC
1/2 hp
Embedded Surge Suppressor
No
Mechanical Operating Durability
10,000,000
Includes Auxiliary Contacts
Yes
Horsepower @ Three Phase - 600V AC
10 hp
Conventional Free Air Thermal Current
20 A (at 50°C Power Circuit), 10 A (at 50°C Signalling Circuit)